{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F4004FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F4004FE7","canonicalUrl":"https://aoctrl.com/schneider/LC1F4004FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F4004FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F4004FE7, 4-pole contactor, 500 A AC-1 at ≤440 V, 115 V AC 40-400 Hz coil, plate mount, IP20 front face.","salesMarkdown":"The Schneider TeSys F LC1F4004FE7 is a 4-pole contactor rated 500 A in AC-1 utilisation category at ≤440 V, making it a fit for resistive heating loads, lighting banks, and non-inductive switching where the current curve stays steady. The 115 V AC coil (40-400 Hz) draws 1075 VA inrush, then holds at 15 VA — the drop-out threshold sits between 0.3 and 0.5 Uc, so a brownout below about 57 V will release the armature cleanly. The 500 A AC-1 rating governs resistive loads — heaters, furnaces, lamp banks. For motor duty (AC-3), the contactor would derate significantly; the datasheet does not list an AC-3 figure, so if the load is a motor, this is the wrong utilisation category. The 4 NO poles are all normally-open; there are no NC auxiliary contacts built in, so a separate control relay or auxiliary contact block is needed for a holding circuit. Plate-mounted, not DIN-rail — the 261 mm width and 219 mm depth require a drilled backplate or sub-panel. Power connections use bar (30 x 5 mm busbar) or ring-lug terminals up to 150 mm² cable; control wiring is screw-clamp, 1 to 4 mm² flexible or solid. Tightening torque for the power circuit is 35 N.m — a torque wrench is expected. The 14 W heat dissipation at rated current needs ventilation clearance in the enclosure; stacking multiple units without spacing will raise internal temperature above the 55 °C operating limit. Designed and tested to IEC 60947-4-1 and EN 60947-4-1, the contactor carries a rated insulation voltage of 1000 V (IEC) and an impulse withstand of 8 kV. The protective treatment (TH) indicates tropicalisation — the coil and magnetic circuit are treated against humidity and corrosion, which matters for unheated warehouses or coastal plants.","metaTitle":"Schneider TeSys F LC1F4004FE7 Contactor, 500A AC-1, 115VAC C","metaDescription":"Schneider TeSys F LC1F4004FE7 4-pole contactor, 500A AC-1 rated, 115VAC 40-400Hz coil. EOL lifecycle. Sourced to order against RFQ. IEC/EN 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"219 mm","Range":"TeSys","Width":"261 mm","Height":"206 mm","Standards":"JIS C8201-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1","Operating time":"40...65 ms closing 100...170 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"14 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.26 mOhm - Ith 500 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"1075 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"400 A aM at 500 A gG at <= 440 V","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm Power circuit: lugs-ring terminals 2 cable(s) 150 mm²","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"3200 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"65 W AC-1","[Uc] control circuit voltage":"115 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"500 A (at <40 °C) at <= 440 V AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"15 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3600 A 40 °C - 10 s 2400 A 40 °C - 30 s 1700 A 40 °C - 1 min 1200 A 40 °C - 3 min 1000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"500 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7a579c57b8f84e1752c2c2a5be1e0642.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1F4004FE7/tesys-f-contactor-4p-4-no-ac1-440-v-500-a-coil-115-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F4004FE7/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for the LC1F4004FE7?","answer":"The contactor is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. The rated insulation voltage is 1000 V per IEC 60947-4-1, with an 8 kV impulse withstand. The IP20 front face conforms to IEC 60529 and VDE 0106."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F4004FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F4004FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}