{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F400FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F400FE7","canonicalUrl":"https://aoctrl.com/schneider/LC1F400FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F400FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F400FE7, 3-pole contactor, 500 A AC-3 at ≤440 V, 115 V AC 50/60 Hz coil, plate mount.","salesMarkdown":"The Schneider Electric LC1F400FE7 is a TeSys F 3-pole contactor rated for 500 A operational current in AC-3 duty at ≤440 V, with a 115 V AC 50/60 Hz control coil. It is designed for direct on-line motor starting and resistive load switching, covering motor power up to 200 kW at 380–400 V AC-3 and 75 kW at 400 V AC-4. The 500 A AC-3 rating at ≤440 V governs motor switching duty — this contactor handles a 200 kW, 380–400 V induction motor on a conveyor or pump, or a 250 kW unit at 440 V. The 115 V AC coil draws 1075 VA inrush at 20 °C, with a hold-in range of 0.85–1.1 Uc and drop-out between 0.3–0.5 Uc — important for control transformer sizing and undervoltage release coordination. The contactor dissipates 14 W total (65 W per pole in AC-1, 42 W per pole in AC-3), which factors into enclosure thermal management. Plate mounting is specified — no DIN-rail clip, so panel layout must account for bolted-down footprint. The LC1F400FE7 is certified to IEC 60947-1, IEC 60947-4-1, EN 60947-4-1, JIS C8201-4-1, and EN 60947-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III applies. The front face achieves IP20 with shrouds fitted, per IEC 60529 and VDE 0106. Protective treatment is TH (tropicalized) for humid environments.","metaTitle":"Schneider Electric LC1F400FE7 TeSys F Contactor, 500 A AC-3,","metaDescription":"Schneider Electric LC1F400FE7 TeSys F contactor. 500 A rated operational current (AC-3), 115 VAC 50/60 Hz coil. End-of-life status — sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"219 mm","Range":"TeSys","Width":"213 mm","Height":"206 mm","Standards":"IEC 60947-1 IEC 60947-4-1 EN 60947-4-1 JIS C8201-4-1 EN 60947-1","Motor power kW":"75 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 380...400 V AC 50/60 Hz (AC-3) 220 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 257 kW at 500 V AC 50/60 Hz (AC-3) 280 kW at 660...690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 220...230 V AC 50/60 Hz (AC-3)","Operating time":"40...65 ms closing 100...170 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"14 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.26 mOhm - Ith 500 A 50 Hz","Device short name":"LC1F","Motor Power Range":"110...220 kW at 480...500 V 3 phases 110...220 kW at 380...440 V 3 phases 110...220 kW at 200...240 V 3 phases 250...500 kW at 480...500 V 3 phases","Poles description":"3P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 35 N.m","Compatibility code":"LC1F","Inrush power in VA":"1075 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Motor starter type":"Direct on-line contactor","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Motor control Resistive load","Mechanical durability":"10 Mcycles","Associated fuse rating":"400 A aM at 500 A gG at <= 440 V","Contactor coil voltage":"115 V AC standard","Maximum operating rate":"2400 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm Power circuit: lugs-ring terminals 2 cable(s) 150 mm² Power circuit: bolted connection","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"3200 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"65 W AC-1 42 W AC-3","[Uc] control circuit voltage":"115 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"500 A (at 400 A (at <55 °C) at <= 440 V AC AC-3","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"15 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3600 A 40 °C - 10 s 2400 A 40 °C - 30 s 1700 A 40 °C - 1 min 1200 A 40 °C - 3 min 1000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"500 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/12998ba587ad874d73e94779bfd0e625.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F400FE7/tesys-f-contactor-3p-3-no-ac3-440-v-400-a-coil-115-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F400FE7/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy LC1F400FE7 and how do I get a price?","answer":"We source and quote the LC1F400FE7 to order against an RFQ. Submit a request through the RFQ form on this page; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to LC1F400FE7 in the TeSys F family?","answer":"No official successor order code is listed. Within the TeSys F range, a contactor with the same frame size and coil voltage but a different current rating may be a parametric match — contact us with your motor full-load amps and duty cycle to evaluate a cross-reference."},{"question":"What compliance documentation does Schneider provide for LC1F400FE7?","answer":"The contactor is certified to IEC 60947-1, IEC 60947-4-1, EN 60947-4-1, JIS C8201-4-1, and EN 60947-1. Rated insulation voltage is 1000 V per IEC 60947-4-1. The front face carries IP20 protection with shrouds. Protective treatment is TH (tropicalized)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F400FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F400FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}