{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F5004V7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F5004V7","canonicalUrl":"https://aoctrl.com/schneider/LC1F5004V7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F5004V7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F contactor, LC1F5004V7, 4-pole, 700 A AC-1, 400 VAC 40-400 Hz coil, plate mount, end-of-life.","salesMarkdown":"## Commissioning and Integration Notes The Schneider Electric LC1F5004V7 is a TeSys F contactor with four normally open power poles, rated 700 A in AC-1 utilisation category for resistive loads at ≤ 440 V AC and ≤ 40 °C ambient. The 400 V AC control coil (40-400 Hz) draws 1100 VA inrush and 18 VA hold-in power; operational limits are 0.85 to 1.1 Uc, drop-out between 0.3 and 0.5 Uc. Closing time spans 40-65 ms, opening 100-170 ms, which matters for sequencing interlocks where the slower opening must be factored into safety circuit response. Mounting is plate-based (not DIN rail), with dimensions 288 mm wide × 238 mm high × 232 mm deep. Power circuit connections use bolted bars (up to 40 × 5 mm busbar) or ring lugs up to 240 mm²; control wiring uses screw clamp terminals accepting 1-4 mm² flexible or solid. Tightening torque is 35 N·m on the power circuit and 1.2 N·m on the control circuit — the power torque is substantial, so a calibrated torque wrench is expected during panel build. The LC1F5004V7 is a 4-pole, 700 A AC-1 contactor with a 400 VAC coil. Any drop-in replacement must match the coil voltage, pole count, and mounting footprint. The 700 A AC-1 rating is the headline — this contactor is sized for pure resistive loads (heater banks, lighting, power factor correction capacitor banks) where inrush is low. For motor or inductive loads (AC-3 or AC-4 duty), the rated operational current would be significantly lower; this part is not selected for motor starting without derating. For high-speed switching applications (e.g., resistance welding controls), verify the thermal dissipation: 18 W total, 88 W per pole in AC-1 duty. The associated fuse recommendation is 500 A aM or 800 A gG at ≤ 440 V — this is the short-circuit protection coordination the designer must follow to maintain the contactor's SCCR. The control circuit is AC only (40-400 Hz), not DC — a common mis-selection trap. The 400 V coil voltage is standard for European 400/690 V three-phase systems where the control transformer secondary is 400 V line-to-line. Overvoltage category III and rated insulation voltage of 1000 V (IEC) / 1500 V (VDE) make it suitable for fixed-installation distribution panels with transient overvoltages up to 8 kV impulse withstand. ## Environmental and Compliance Profile The contactor carries TH protective treatment for tropical/humid environments. Altitude derating starts above 3000 m without derating, covering most installations below that. Standards compliance includes IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. These cover the contactor's design, testing, and performance for low-voltage switchgear and controlgear. The evidence does not list UL, CSA, RoHS, or REACH documentation explicitly; verification of those certifications should be requested at the time of RFQ if required for the target jurisdiction.","metaTitle":"Schneider Electric LC1F5004V7 TeSys F Contactor, 700 A AC-1,","metaDescription":"Schneider Electric LC1F5004V7 TeSys F contactor, 700 A AC-1, 4 NO, 400 VAC 40-400 Hz coil. End-of-life status. Sourced to order. Standards: IEC 60947, EN 60947. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"232 mm","Width":"288 mm","Height":"238 mm","Current":"700 A (at <40 °C) at <= 440 V AC AC-1","Voltage":"<= 460 V DC","Application":"Resistive load","Coil Voltage":"400 V AC 40...400 Hz","Operating Time":"40...65 ms closing 100...170 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"4000 A conforming to IEC 60947-4-1","Insulation Voltage Ui":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-1","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...55 °C","Permissible Ambient Air Temperature Around The Device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/17cc359fa3f7f04485c8213203a653fa.pdf","sourceUrl":"https://www.se.com/za/en/product/LC1F5004V7/tesys-f-contactor-4p-4-no-ac1-440-v-700-a-coil-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F5004V7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F5004V7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F5004V7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}