{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F7804FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F7804FE7","canonicalUrl":"https://aoctrl.com/schneider/LC1F7804FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F7804FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F, LC1F7804FE7, 4-pole contactor, 1600 A AC-1, 115 V AC 40-400 Hz coil, plate mount, 862 x 434 x 255 mm.","salesMarkdown":"The LC1F7804FE7: The 1600 A AC-1 rating governs the continuous current-carrying capacity for resistive loads at ≤440 V AC. The 4 NO power poles are all normally-open; for applications needing NC poles or auxiliary contacts, those must be added externally. Control voltage limits are 0.85–1.1 Uc for pickup and 0.2–0.4 Uc for dropout at 55 °C — the coil will hold in down to about 98 V AC and drop out below about 46 V AC. Plate mounting is required; this is not a DIN-rail part. The 862 mm width and 434 mm height mean the panel cutout and enclosure depth must accommodate the full 255 mm depth plus wiring clearance for the 100 x 5 mm busbar connections. The contactor is designed and tested to IEC 60947-4-1 and EN 60947-4-1, the standards for contactors and motor-starters. It also carries JIS C8201-4-1 compliance. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Impulse withstand voltage is 8 kV, overvoltage category III. The front face achieves IP20 with shrouds fitted, per IEC 60529 and VDE 0106. ## Physical Integration Plate-mount only. Power circuit connections use bars with a 100 x 5 mm busbar cross-section; tightening torque is 58 N.m. Control circuit wiring uses screw-clamp terminals accepting 1–4 mm² flexible or solid (1 or 2 cables), torqued to 1.2 N.m. Ambient operating range is -5 to 55 °C; storage range is -60 to 80 °C. Protective treatment is TH for tropical environments.","metaTitle":"Schneider LC1F7804FE7 TeSys F Contactor, 1600 A AC-1, 115 V","metaDescription":"Schneider Electric LC1F7804FE7 TeSys F 4-pole contactor. 1600 A rated operational current (AC-1), 115 V AC 50/60 Hz coil. End-of-life stage; sourced to order against RFQ. IEC/EN 60","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"255 mm","Range":"TeSys","Width":"862 mm","Height":"434 mm","Standards":"EN 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1","Operating time":"40...80 ms closing 130...230 ms opening","lifecycle_stage":"eol_hot","Heat dissipation":"44 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1600 A 50 Hz","Device short name":"LC1F","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 58 N.m","Compatibility code":"LC1F","Inrush power in VA":"2100 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 40...400 Hz","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"5 Mcycles","Associated fuse rating":"1600 A gG at 800 A aM at <= 440 V","Maximum operating rate":"600 cyc/h 55 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm","IP degree of protection":"IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106","Rated breaking capacity":"6240 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Power dissipation per pole":"250 W AC-1","[Uc] control circuit voltage":"115 V AC 40...400 Hz","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.2...0.4 Uc 40...400 Hz (at 55 °C)","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"1600 A (at <40 °C) at <= 440 V AC AC-1","[Ue] rated operational voltage":"<= 460 V DC","Hold-in power consumption in VA":"50 VA, 40...400 Hz cos phi 0.9 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3000 A 40 °C - 3 min 6250 A 40 °C - 10 s 5600 A 40 °C - 30 s 4600 A 40 °C - 1 min 2200 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1600 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3c1f019791a2f92786d1c8cbddc6fc5b.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F7804FE7/tesys-f-contactor-4p-4-no-ac1-440-v-1600-a-coil-115-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F7804FE7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1F7804FE7 in the TeSys F family?","answer":"No official successor order code is documented for this specific variant. Within the TeSys F range, a functionally similar contactor would need to match the 1600 A AC-1 rating, 4 NO pole configuration, 115 V AC coil, and plate-mount form factor. Any substitution requires verifying the exact BOM requirements and should be confirmed against the customer's approved manufacturer list (AML)."},{"question":"Where can I buy LC1F7804FE7 and get current pricing?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F7804FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F7804FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}