{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F7804P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F7804P7","canonicalUrl":"https://aoctrl.com/schneider/LC1F7804P7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F7804P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F7804P7, 4-pole contactor, 1600 A AC-1, 230 VAC 40-400 Hz coil, 4 NO, plate mount, EOL phase-out.","salesMarkdown":"## 1600 A AC-1 Contactor — What This Rating Means The Schneider Electric LC1F7804P7 is a TeSys F 4-pole contactor rated 1600 A in AC-1 utilisation category at ≤ 440 V, meaning it is sized for switching resistive heating loads, lighting banks, or transformer primaries — not motor starts. The AC-1 rating governs the continuous current the main poles carry without derating; for motor duty (AC-3), the same contactor would be rated significantly lower. The 4 NO power pole configuration gives four normally-open main contacts, all rated for the full 1600 A. The 230 VAC control coil draws 2100 VA inrush at pickup, dropping to 50 VA hold-in — the inrush surge matters for control transformer sizing in the panel. ## Mounting and Integration — Plate-Mount, Not DIN Rail Mounting support is plate — this contactor does not snap onto a DIN rail. The footprint is substantial: 862 mm wide, 434 mm high, 255 mm deep. Power circuit connections use bolted busbars rated for 100 x 5 mm cross-section; control circuit connections are screw clamp terminals accepting 1 to 4 mm² flexible or solid wire. Tightening torque for power circuit connections is 58 N.m, control circuit 1.2 N.m. Designed and certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C. Impulse withstand voltage (Uimp) is 8 kV, overvoltage category III. The protective treatment is TH for tropicalized environments — suitable for humid or corrosive atmospheres when panel conditions are controlled.","metaTitle":"Schneider LC1F7804P7 TeSys F Contactor, 1600 A AC-1, 4 NO, 2","metaDescription":"Schneider Electric LC1F7804P7 TeSys F 4-pole contactor, 1600 A AC-1, 230 VAC coil, 4 NO. EOL phase-out. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"255 mm","Width":"862 mm","Height":"434 mm","Current":"1600 A (at <40 °C) at <= 440 V AC AC-1","Voltage":"<= 460 V DC","Application":"Resistive load","Coil Voltage":"230 V AC 40...400 Hz","Operating Time":"40...80 ms closing 130...230 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"6240 A conforming to IEC 60947-4-1","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-1","Mechanical Life Cycles":"5 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...55 °C","Permissible Ambient Air Temperature Around The Device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/949ddf21c2333542ddf99f1c244d7356.pdf","sourceUrl":"https://www.se.com/th/en/product/LC1F7804P7/contactor-tesys-f-4p4no-ac1-440v-1600a-coil-230v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F7804P7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F7804P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F7804P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}