{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1F780FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1F780FE7","canonicalUrl":"https://aoctrl.com/schneider/LC1F780FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1F780FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F LC1F780FE7, direct on-line contactor, 3 poles, 450 kW at 1000 V AC-3, 115 V AC 40-400 Hz coil, plate mount, 702 x 434 x 255 mm.","salesMarkdown":"The 115 V AC coil (40-400 Hz) pulls 2100 VA inrush at 20 °C; the control circuit holds within 0.85 to 1.1 Uc and drops out between 0.2 and 0.4 Uc. Three normally-open power poles, 1600 A rated operational current at ≤ 440 V AC-3, with a rated breaking capacity of 6240 A per IEC 60947-4-1. The 0.1 mOhm impedance at 1600 A 50 Hz means pole dissipation runs 60 W per pole in AC-3 and 250 W in AC-1 — heat that must be vented in the enclosure. Plate-mounted, 702 mm wide by 434 mm high by 255 mm deep. Power circuit bolted connections accept busbars up to 100 x 5 mm; control circuit screw-clamp terminals take 1 to 4 mm² flexible or solid. Tightening torque is 58 N·m on the power side, 1.2 N·m on control. IP20 front face with shrouds per IEC 60529. ## Deployment context This contactor is sized for heavy motor control in industrial panels — think large pumps, compressors, conveyors, or crushers on 400 V to 1000 V three-phase systems. The 3000 m operating altitude without derating suits high-altitude installations. Overvoltage category III means it is designed for fixed-installation distribution-level transients. The TH protective treatment indicates a tropicalized coating for humidity and corrosive atmospheres. Certified to IEC 60947-4-1, IEC 60947-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Associated fuse rating 1600 A gG or 800 A aM at ≤ 440 V. Mechanical durability 5 million cycles; maximum operating rate 600 cycles per hour at 55 °C.","metaTitle":"Schneider Electric LC1F780FE7 TeSys F Contactor, 450 kW AC-3","metaDescription":"Schneider Electric LC1F780FE7 TeSys F contactor, 450 kW at 1000 V AC-3, 115 VAC coil. EOL phase. Sourced to order against RFQ. IEC 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"255 mm","Width":"702 mm","Height":"434 mm","Current":"1600 A (at 780 A (at <55 °C) at <= 440 V AC AC-3","Voltage":"<= 460 V DC","Application":"Resistive load Motor control","Coil Voltage":"115 V AC 40...400 Hz","Operating Time":"40...80 ms closing 130...230 ms opening","Product Status":"End of Life","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Breaking Capacity":"6240 A conforming to IEC 60947-4-1","Motor Starter Type":"Direct on-line contactor","Temp Operating Max":"55 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Control Circuit Type":"AC at 40...400 Hz","Utilization Category":"AC-3 AC-1 AC-4","Mechanical Life Cycles":"5 Mcycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...55 °C","Permissible Ambient Air Temperature Around The Device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/52b1a5e3b12b86cbe663ed19529f3848.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1F780FE7/contactor-tesys-f-3p3no-ac3-440v-780a-coil-115v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1F780FE7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1F780FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1F780FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}