{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G1154EHEA","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G1154EHEA","canonicalUrl":"https://aoctrl.com/schneider/LC1G1154EHEA","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G1154EHEA","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga, Contactor, 4P, 115A AC-3, 48-130VAC/DC, IP2X front face.","salesMarkdown":"The Schneider Electric LC1G1154EHEA is a 4-pole contactor from the TeSys Giga range, rated for power switching in motor and resistive loads per utilization categories AC-3, AC-3e, AC-1, and several others. Its AC-3 continuous current rating is 115 A per pole, dissipating 3 W per pole at that load, and it can handle 250 A in AC-1 resistive duty with 10 W per pole dissipation. ## Ratings that drive the fit With 4 normally open poles, this contactor switches three-phase motors without a neutral or can be wired for separate load groups. The 115 A AC-3 rating means it comfortably handles a 75 hp motor at 460/480 V (per the horsepower table) while staying within the rated breaking capacity of 1040 A at 440 V and making capacity of 1560 A.","metaTitle":"Schneider Electric LC1G1154EHEA TeSys Giga Contactor, 4P, 11","metaDescription":"Active 4-pole power contactor rated 115 A AC-3, 48-130 V AC/DC coil. UL, CSA, IEC 60947. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"5.6 in (143 mm)","Height":"10.04 in (255 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00018 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"125 A aM at 125 A aM at 315 A gG at 300 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"190 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1040 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1560 A at 440 V","Maximum Horse Power Rating":"30 hp at 200/208 V 60 Hz 40 hp at 230/240 V 60 Hz 75 hp at 460/480 V 60 Hz 100 hp at 575/600 V 60 Hz","Power dissipation per pole":"10 W AC-1 - Ith 250 A 3 W AC-3 - Ith 115 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"115 A (at 250 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"260 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"5.0 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.1 kA - 10 s 0.64 kA - 30 s 0.52 kA - 1 min 0.4 kA - 3 min 0.32 kA - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,055.00 – $1,365.03","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5c1c38d2b1bf83be79f3c2f1ce6f2809.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G1154EHEA/alternatives.json"},"ai":{"faq":[{"question":"What standards does this contactor comply with?","answer":"It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40 Annex JJ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G1154EHEA","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G1154EHEA when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}