{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G115KUEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G115KUEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G115KUEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G115KUEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider LC1G115KUEN Iec Contactors 66 Over Amp.","salesMarkdown":"## Overview The LC1G115KUEN is a 3-pole IEC contactor from the Schneider TeSys Giga range, rated for 250 A switching current on a 460 V supply. The coil pulls in at 250 V AC and uses built-in bidirectional peak limiting to suppress switching transients without external suppression modules. It carries 1 NO + 1 NC auxiliary contacts and is certified to EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, covering global panel approvals. ## Sizing and selection The 250 A switching current and 1.04 kA breaking capacity place the LC1G115KUEN at the lower end of the TeSys Giga frame. For a BOM that originally specified the LC1G225EHEA (330 A switching, 2.05 kA breaking), the LC1G115KUEN will not drop in without rewiring — the terminal pitch is 35 mm on both, but the LC1G225EHEA draws 8.9 W holding power versus 12.4 W for the LC1G115KUEN, and the coil voltage differs. Verify the control circuit and load current before substituting. The LC1G115KUEN is an active TeSys Giga catalog part. Lead time is quoted per RFQ; no end-of-life notice is published as of the latest Schneider lifecycle data.","metaTitle":"Schneider LC1G115KUEN TeSys Giga contactor, 3-pole, 250 A, 250 V coil","metaDescription":"Schneider LC1G115KUEN TeSys Giga IEC contactor, 3-pole, 250 A switching, 250 V AC coil with peak limiting, 1 NO + 1 NC aux, 1.04 kA breaking capacity, EN/IEC/UL/CSA certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"4.3 in (108 mm)","Height":"7.6 in (193 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","Motor power kW":"30 kW at 230 V AC 50/60 Hz (AC-3e) 55 kW at 400 V AC 50/60 Hz (AC-3e) 55 kW at 415 V AC 50/60 Hz (AC-3e) 75 kW at 440 V AC 50/60 Hz (AC-3e) 75 kW at 500 V AC 50/60 Hz (AC-3e) 75 kW at 690 V AC 50/60 Hz (AC-3e) 30 kW at 230 V AC 50/60 Hz (AC-3) 55 kW at 400 V AC 50/60 Hz (AC-3) 55 kW at 415 V AC 50/60 Hz (AC-3) 75 kW at 440 V AC 50/60 Hz (AC-3) 75 kW at 500 V AC 50/60 Hz (AC-3) 75 kW at 690 V AC 50/60 Hz (AC-3) 30 kW at 230 V AC 50/60 Hz (AC-4) 55 kW at 400 V AC 50/60 Hz (AC-4) 55 kW at 415 V AC 50/60 Hz (AC-4) 65 kW at 440 V AC 50/60 Hz (AC-4) 65 kW at 500 V AC 50/60 Hz (AC-4) 75 kW at 690 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00018 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"125 A aM at 125 A aM at 315 A gG at 300 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"380 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1040 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1560 A at 440 V","Maximum Horse Power Rating":"30 hp at 200/208 V 60 Hz 40 hp at 230/240 V 60 Hz 75 hp at 460/480 V 60 Hz 100 hp at 575/600 V 60 Hz","Power dissipation per pole":"10 W AC-1 - Ith 250 A 3 W AC-3 - Ith 115 A","[Uc] control circuit voltage":"100...250 V AC 50/60 Hz 100...250 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"250 A (at 115 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"540 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"7.8 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.1 kA - 10 s 0.64 kA - 30 s 0.52 kA - 1 min 0.4 kA - 3 min 0.32 kA - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$833.51","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5c1c38d2b1bf83be79f3c2f1ce6f2809.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G115KUEN/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G115KUEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G115KUEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}