{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G150LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G150LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G150LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G150LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G150LSEN, 3-pole contactor, 75 kW at 400 V AC-3e, coil 200...500 V AC/DC, dark grey.","salesMarkdown":"The Schneider Electric TeSys Giga LC1G150LSEN is a 3-pole contactor rated for motor switching up to 75 kW at 400 V AC in both AC-3 and AC-3e duty classes — the e-suffix means it's tested to the enhanced electrical endurance profile for IEC contactors. At 460/480 V 60 Hz it carries a 100 hp rating, so it fits North American motor schedules as well. The coil accepts 200...500 V AC or DC, which simplifies panel wiring when the control voltage is shared across a mixed AC/DC bus. AC-3e at 75 kW / 400 V is the headline motor-switching rating — it handles the starting inrush and breaking of a squirrel-cage motor under normal duty. The same contactor also lists AC-4 at 75 kW / 400 V, which covers plugging and inching where the contactor opens under full locked-rotor current. That dual rating means this part can serve both standard start/stop and reversing or jogging applications without oversizing. The average impedance per pole is 0.00018 ohm, which keeps voltage drop low under full load. For high-speed cycling applications like indexing conveyors, that rate is the practical ceiling. The LC1G150LSEN is a panel-mount contactor — plate-mount support, with a connection pitch of 35 mm between phases. Power terminals accept bar or busbar up to 25 x 6 mm, or lugs up to 185 mm². Tightening torque for the power connections is 18 N.m. Front face with shrouds carries IP2X protection per IEC 60529 and VDE 0106 — finger-safe against accidental contact. The TH protective treatment means it's coated for tropical/humid environments, which matters for unheated enclosures or washdown areas. This contactor carries compliance with EN/IEC 60947-4-1 and EN/IEC 60947-5-1 (the main contactor and aux contact standards), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American acceptance. It also meets JIS C8201-4-1 and JIS C8201-5-1 for Japanese installations, and the IEC 60335 series for appliance applications.","metaTitle":"Schneider Electric TeSys Giga LC1G150LSEN Contactor, 3P, 75","metaDescription":"Schneider Electric TeSys Giga LC1G150LSEN 3-pole contactor. Motor power 75 kW at 400 V AC-3e. Coil 200-500 V AC/DC. Complies with IEC/EN 60947-4-1, UL 60947-4-1. Current production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"4.3 in (108 mm)","title":"LC1G150LSEN","Height":"7.6 in (193 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","description":"Contactor, high power, TeSys Giga, 3P(3NO), AC-3, <=440V 150A, standard version, 200-500V AC/DC wide band coil","Motor power kW":"37 kW at 230 V AC 50/60 Hz (AC-3e) 75 kW at 400 V AC 50/60 Hz (AC-3e) 75 kW at 415 V AC 50/60 Hz (AC-3e) 90 kW at 440 V AC 50/60 Hz (AC-3e) 90 kW at 500 V AC 50/60 Hz (AC-3e) 90 kW at 690 V AC 50/60 Hz (AC-3e) 75 kW at 1000 V AC 50/60 Hz (AC-3e) 37 kW at 230 V AC 50/60 Hz (AC-3) 75 kW at 400 V AC 50/60 Hz (AC-3) 75 kW at 415 V AC 50/60 Hz (AC-3) 90 kW at 440 V AC 50/60 Hz (AC-3) 90 kW at 500 V AC 50/60 Hz (AC-3) 90 kW at 690 V AC 50/60 Hz (AC-3) 75 kW at 1000 V AC 50/60 Hz (AC-3) 37 kW at 230 V AC 50/60 Hz (AC-4) 75 kW at 400 V AC 50/60 Hz (AC-4) 75 kW at 415 V AC 50/60 Hz (AC-4) 80 kW at 440 V AC 50/60 Hz (AC-4) 90 kW at 500 V AC 50/60 Hz (AC-4) 90 kW at 690 V AC 50/60 Hz (AC-4) 75 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00018 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"160 A aM at 160 A aM at 315 A gG at 300 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"215 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"1280 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1890 A at 440 V","Maximum Horse Power Rating":"40 hp at 200/208 V 60 Hz 50 hp at 230/240 V 60 Hz 100 hp at 460/480 V 60 Hz 125 hp at 575/600 V 60 Hz","Power dissipation per pole":"10 W AC-1 - Ith 275 A 5 W AC-3 - Ith 150 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"275 A (at 150 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"295 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"8 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.2 kA - 10 s 0.7 kA - 30 s 0.6 kA - 1 min 0.45 kA - 3 min 0.35 kA - 10 min","[Ith] conventional free air thermal current":"275 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$850.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/91c0e9c256574afdadb67ba7ebbb023d.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1G150LSEN/contactor-high-power-tesys-giga-3p3no-ac3-440v-150a-standard-version-200500v-ac-dc-wide-band-coil/"},"ai":{"faq":[{"question":"What compliance documentation does this contactor carry?","answer":"It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, IEC 60335-1 Clause 30.2, IEC 60335-2-40 Annex JJ, UL 60335-1, and UL 60335-2-40 Annex JJ."},{"question":"What is the coil voltage range for this contactor?","answer":"The control circuit voltage is 200...500 V AC 50/60 Hz and 200...500 V DC. The coil uses built-in bidirectional peak limiting, so it handles both AC and DC supplies without external suppression."},{"question":"What is the closest alternative in the same family?","answer":"Within the TeSys Giga range, the LC1G150LSEN is a 3-pole contactor with a 200-500 V AC/DC coil. Other members of the LC1G family share the same footprint and connection pitch but differ in coil voltage and auxiliary contact configuration. For a direct coil-voltage swap, look at other LC1G variants with the same control circuit range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G150LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G150LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}