{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G2254EHEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G2254EHEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G2254EHEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G2254EHEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G2254EHEN, 4-pole power contactor, 225 A AC-3, 48-130 V coil, dark grey enclosure.","salesMarkdown":"That 225 A figure (: AC-3 Ith) is the one you'll spec against a motor's full-load amps — not the 330 A AC-1 resistive number. Coil is dual-voltage: 48 to 130 V AC or DC, so one part covers both line and control circuits in a mixed panel. Mechanical durability is 8 million cycles, and the contactor is rated for vibrations up to 4 gn closed and shocks of 15 gn — meaning it stays pulled in on a portable generator skid or a compressor baseplate. The integral bidirectional peak-limiting coil technology reduces inrush to 445 W DC, which keeps power supply sizing predictable. Power circuit terminals accept busbar cross-section up to 25 x 6 mm or ring lugs up to 185 mm². Control circuit uses push-in terminals sized for 0.2 to 2.5 mm², which matches common PLC output wiring. Mounting is plate-mount with a 35 mm pitch between poles — plan for the 193 mm depth when laying out the backplate. IP2X with shrouds: safe for front-face access inside a locked panel. Associated fuse recommendations: 250 A aM or 400 A gG for short-circuit protection at 600 V, with a UL Type J option. Rated making capacity is 2720 A at 440 V, breaking capacity 2050 A at 440 V — figures that matter for coordination studies on high-fault panels. Listed to EN/IEC 60947-4-1 and -5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus JIS and UL appliance standards (UL 60335). Overvoltage category III. The protective treatment 'TH' indicates tropicalisation for humid environments. Standards compliance covers the documentation a tender buyer typically requires.","metaTitle":"LC1G2254EHEN Contactor, 225 A AC-3, 4-Pole","metaDescription":"Current-production 4-pole contactor from TeSys Giga. 225 A AC-3, 48-130 V coil, UI 1000 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"5.6 in (143 mm)","Height":"7.6 in (193 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00015 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"250 A aM at 200 A aM at 400 A gG at 400 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"445 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2050 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"2720 A at 440 V","Power dissipation per pole":"20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"225 A (at 330 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"640 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"7.8 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min","[Ith] conventional free air thermal current":"330 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/46ac3abe631ae2c273ef50f0c970a124.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G2254EHEN/alternatives.json"},"ai":{"faq":[{"question":"What is LC1G2254EHEN's listed color?","answer":"The enclosure is dark grey."},{"question":"What is LC1G2254EHEN's listed depth?","answer":"It is 7.6 inches (193 mm) deep."},{"question":"What compliance documentation is available for LC1G2254EHEN?","answer":"The contactor complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS standards, among others."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G2254EHEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G2254EHEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}