{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G2254LSEA","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G2254LSEA","canonicalUrl":"https://aoctrl.com/schneider/LC1G2254LSEA","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G2254LSEA","rawCanonicalId":null},"summary":{"shortDescription":"TeSys Giga, 4-pole contactor, LC1G2254LSEA, 225 A AC-3, coil 200-500 V AC/DC, dark grey.","salesMarkdown":"It carries four normally-open power poles and one built-in NO plus one NC auxiliary contact. Power connections use bolted lugs or busbar rated for 185 mm² cross-section; control circuit terminals are push-in style accepting 0.2 to 2.5 mm² solid or stranded wire. Tightening torque for power terminals is 18 N·m. Mounting is plate-based, with a pitch of 35 mm between pole centers. The overall footprint is 143 mm wide by 255 mm tall by 193 mm deep, and the front face with shrouds achieves IP2X protection. ## Utilization and performance Beyond AC-3 motor duty, this contactor is also listed for AC-1 resistive, AC-3e, AC-5a, AC-5b, AC-6a, and AC-6b categories. Rated making capacity 2720 A at 440 V, breaking capacity 2050 A, mechanical durability 8 Mcycles, max operating rate 600 cyc/h AC-3, and power dissipation 20 W per pole at AC-1 330 A.","metaTitle":"LC1G2254LSEA TeSys Giga 4-Pole Contactor, 225 A AC-3","metaDescription":"TeSys Giga LC1G2254LSEA 4-pole contactor rated 225 A in AC-3 motor duty. Coil 200-500 V AC/DC with built-in peak limiting. Current production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"5.6 in (143 mm)","Height":"10.04 in (255 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00015 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"250 A aM at 200 A aM at 400 A gG at 400 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"215 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2050 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"2720 A at 440 V","Power dissipation per pole":"20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"225 A (at 330 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"295 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"8.0 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min","[Ith] conventional free air thermal current":"330 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,860.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/46ac3abe631ae2c273ef50f0c970a124.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G2254LSEA/alternatives.json"},"ai":{"faq":[{"question":"What is LC1G2254LSEA's listed color?","answer":"It is dark grey."},{"question":"What is LC1G2254LSEA's listed depth?","answer":"The depth is 7.6 inches (193 mm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G2254LSEA","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G2254LSEA when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}