{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G225EHEA","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G225EHEA","canonicalUrl":"https://aoctrl.com/schneider/LC1G225EHEA","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G225EHEA","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric LC1G225EHEA TeSys Giga 3-pole contactor, 225 A AC-3e, 160 kW at 690 V, 48–130 V AC/DC coil with built-in bidirectional peak limiting.","salesMarkdown":"Schneider LC1G225EHEA TeSys Giga three-pole contactor rated for motor loads up to 160 kW at 690 V AC-3e and 132 kW at 1000 V AC-3e. Coil accepts 48–130 V AC/DC with built-in bidirectional peak limiting. Power circuit connections are bolted bars accepting up to 185 mm² lug or 25 x 6 mm busbar. Control wiring uses push-in terminals (0.2–2.5 mm²) for fast tool-free termination. Auxiliary contact block is built in: 1 NO + 1 NC. ## Mounting and fit The contactor mounts to a plate (not DIN rail) and measures 7.6 x 4.3 x 10.04 inches (depth/width/height). Pole spacing is 35 mm, matching TeSys Giga busbar adapters. Tightening torque for power terminals is 18 N·m — a 3/8” hex driver is fine. Front face with shrouds gives IP2X touch protection (VDE 0106). The housing is dark grey (not the ordinary light grey of TeSys D), so the panel bill of materials will note a colour change if you’re swapping. ## Ratings in use Associated fuse protection: 250 A aM, 400 A gG, or UL Type J at ≤600 V. Rated breaking capacity is 2050 A at 440 V; making capacity is 2720 A at 440 V — enough for high-inrush motor starts. The LC1G225EHEA is a standard catalogue item, quoted to order. For BOM freeze or line-down replacement, submit an RFQ with your target delivery window. No known last-time-buy or PCN at publication.","metaTitle":"Schneider LC1G225EHEA TeSys Giga Contactor, 3-Pole, 48-130V","metaDescription":"Active production TeSys Giga contactor, 225 A AC-3e, 160 kW at 690 V. 48–130 V AC/DC coil with built-in peak limiting. IEC/UL/CSA. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"4.3 in (108 mm)","Height":"10.04 in (255 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","Motor power kW":"55 kW at 230 V AC 50/60 Hz (AC-3e) 110 kW at 400 V AC 50/60 Hz (AC-3e) 110 kW at 415 V AC 50/60 Hz (AC-3e) 132 kW at 440 V AC 50/60 Hz (AC-3e) 132 kW at 500 V AC 50/60 Hz (AC-3e) 160 kW at 690 V AC 50/60 Hz (AC-3e) 132 kW at 1000 V AC 50/60 Hz (AC-3e) 55 kW at 230 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 132 kW at 440 V AC 50/60 Hz (AC-3) 132 kW at 500 V AC 50/60 Hz (AC-3) 160 kW at 690 V AC 50/60 Hz (AC-3) 132 kW at 1000 V AC 50/60 Hz (AC-3) 55 kW at 230 V AC 50/60 Hz (AC-4) 110 kW at 400 V AC 50/60 Hz (AC-4) 110 kW at 415 V AC 50/60 Hz (AC-4) 129 kW at 440 V AC 50/60 Hz (AC-4) 132 kW at 500 V AC 50/60 Hz (AC-4) 132 kW at 690 V AC 50/60 Hz (AC-4) 110 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00015 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"250 A aM at 200 A aM at 400 A gG at 400 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"190 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2050 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"2720 A at 440 V","Maximum Horse Power Rating":"60 hp at 200/208 V 60 Hz 75 hp at 230/240 V 60 Hz 150 hp at 460/480 V 60 Hz 150 hp at 575/600 V 60 Hz","Power dissipation per pole":"20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"330 A (at 225 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"260 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"5.0 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min","[Ith] conventional free air thermal current":"330 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,430.00 – $1,681.48","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/46ac3abe631ae2c273ef50f0c970a124.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G225EHEA/alternatives.json"},"ai":{"faq":[{"question":"What colour is the LC1G225EHEA housing?","answer":"Dark grey. This differs from the standard light grey of TeSys D contactors."},{"question":"What compliance certifications does the LC1G225EHEA carry?","answer":"IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, JIS, and appliance standards including IEC/UL 60335. Protective treatment TH for tropical environments."},{"question":"Does the LC1G225EHEA require an external surge suppressor?","answer":"No. It has a built-in bidirectional peak limiting coil circuit, so no external RC snubber or varistor is needed across the coil terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G225EHEA","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G225EHEA when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}