{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G225LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G225LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G225LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G225LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G225LSEN, 3-pole contactor, 110 kW at 400 V AC-50/60 Hz (AC-3e), dual AC/DC coil 200-500 V, dark grey.","salesMarkdown":"## What this contactor is rated for The Schneider Electric LC1G225LSEN is a 3-pole TeSys Giga contactor rated for motor switching at 110 kW on 400 V AC-3e duty — that is the standard European motor-rating curve, so it handles full-load current for a 110 kW induction motor at that voltage. On AC-4 (reversing, plugging, inching) it still carries 110 kW at 400 V, which is unusual; most contactors derate significantly for AC-4. Built-in bidirectional peak limiting on the coil means you do not need external suppression for the control circuit — the contactor handles its own inrush and back-EMF. Closing time is 40-70 ms, opening 15-50 ms, fast enough for most motor-start and safety-disconnect sequences. ## Standards and approvals — what certs mean for your panel This contactor carries EN/IEC 60947-4-1 (the main contactor standard), UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. That means it is accepted for IEC, North American, and Japanese installations — one part for global machinery if your panel ships to multiple regions. It also meets IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ for appliance and HVAC applications, so it works in heat-pump or air-handler circuits that require glow-wire and tracking resistance. Overvoltage category III means it is rated for fixed-installation distribution-level surges — not just downstream equipment. The TH protective treatment indicates tropicalization against humidity and corrosion, which matters for marine or coastal environments. Lifecycle status is current production. ## Mounting, wiring, and mechanical limits Mounts to a plate — not DIN-rail, so plan for bolted or screw-down installation. Power terminals accept bar (25 x 6 mm busbar), ring lugs up to 185 mm², or bolted connections. Tightening torque is 18 N·m (159.3 lbf·in) on the power terminals — that is substantial; use a torque wrench. IP2X front face with shrouds means finger-safe but not sealed; keep it inside an enclosure. Mechanical durability is 8 million cycles — that is a high-endurance frame. Maximum operating rate is 600 cycles/hour for AC-3 and AC-3e, 300 for AC-1, and 150 for AC-4. The AC-4 rate is the limiting factor for reversing or jogging applications. ## Thermal and protection data Power dissipation per pole: 20 W at AC-1 (Ith 330 A), 8 W at AC-3 (Ith 225 A). Average impedance per pole is 0.00015 Ω, so voltage drop is negligible at rated current. Associated fuse ratings: 250 A aM (motor-protection) or 400 A gG (general-purpose) at 400 V; for UL installations, Type J up to 600 V. Rated breaking capacity is 2050 A at 440 V, making capacity 2720 A at 440 V — these are the short-circuit values the contactor can interrupt or close onto. ## Safety and auxiliary contacts Built-in 1 NO + 1 NC auxiliary contact — enough for a feedback signal to a PLC or a holding circuit. Safety reliability: B10d = 400,000 cycles at nominal load (EN/ISO 13849-1), or 3,000,000 cycles with mechanical load only. That is relevant if you are using the contactor in a safety-related control system and need to calculate PFHd.","metaTitle":"Schneider LC1G225LSEN TeSys Giga Contactor, 110 kW at 400 V","metaDescription":"Schneider Electric LC1G225LSEN TeSys Giga contactor, 3-pole, 110 kW at 400 V AC-3e. Active production. Dual AC/DC coil 200-500 V. UL/CSA/IEC certified. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"7.6 in (193 mm)","Range":"TeSys","Width":"4.3 in (108 mm)","title":"LC1G225LSEN","Height":"7.6 in (193 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","description":"High power contactor,TeSys Giga,3P(3NO),AC-3 <=440V 225A,standard version,200-500V AC/DC wide band coil","Motor power kW":"55 kW at 230 V AC 50/60 Hz (AC-3e) 110 kW at 400 V AC 50/60 Hz (AC-3e) 110 kW at 415 V AC 50/60 Hz (AC-3e) 132 kW at 440 V AC 50/60 Hz (AC-3e) 132 kW at 500 V AC 50/60 Hz (AC-3e) 160 kW at 690 V AC 50/60 Hz (AC-3e) 132 kW at 1000 V AC 50/60 Hz (AC-3e) 55 kW at 230 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 132 kW at 440 V AC 50/60 Hz (AC-3) 132 kW at 500 V AC 50/60 Hz (AC-3) 160 kW at 690 V AC 50/60 Hz (AC-3) 132 kW at 1000 V AC 50/60 Hz (AC-3) 55 kW at 230 V AC 50/60 Hz (AC-4) 110 kW at 400 V AC 50/60 Hz (AC-4) 110 kW at 415 V AC 50/60 Hz (AC-4) 129 kW at 440 V AC 50/60 Hz (AC-4) 132 kW at 500 V AC 50/60 Hz (AC-4) 132 kW at 690 V AC 50/60 Hz (AC-4) 110 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.4 in (35 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.00015 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"159.3 lbf.in (18 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5 AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"250 A aM at 200 A aM at 400 A gG at 400 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"215 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2050 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"2720 A at 440 V","Maximum Horse Power Rating":"60 hp at 200/208 V 60 Hz 75 hp at 230/240 V 60 Hz 150 hp at 460/480 V 60 Hz 150 hp at 575/600 V 60 Hz","Power dissipation per pole":"20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"330 A (at 225 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"295 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"8 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min","[Ith] conventional free air thermal current":"330 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,330.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/792210823dfc1d635ff87dd117edab3a.pdf","sourceUrl":"https://www.se.com/ca/en/product/LC1G225LSEN/high-power-contactortesys-giga3p3noac3-440v-225astandard-version200500v-ac-dc-wide-band-coil/"},"ai":{"faq":[{"question":"What is the closest alternative to LC1G225LSEN in the same family?","answer":"Within the TeSys Giga range, the LC1G225LSEN is a specific coil-voltage variant (200-500 V AC/DC). The mechanical and power ratings are shared across the LC1G225 frame; the coil variant is the differentiating factor. For a different control voltage, select the corresponding LC1G225xxEN where xx denotes the coil code."},{"question":"What compliance documentation is available for LC1G225LSEN?","answer":"The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. It also meets IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ. Schneider Electric provides a Declaration of Conformity covering these standards; request it with your RFQ."},{"question":"What are the physical dimensions of LC1G225LSEN?","answer":"Depth is 193 mm (7.6 in), width is 108 mm (4.3 in), height is 193 mm (7.6 in). Color is dark grey."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G225LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G225LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}