{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G250DCEHEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G250DCEHEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G250DCEHEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G250DCEHEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G250DCEHEN, 3-pole DC contactor, 250 A DC-1, coil 48-130 V AC/DC, IP2X front face.","salesMarkdown":"The LC1G250DCEHEN: The 250 A DC-1 rating governs resistive loads; for motor or inductive DC loads you'd need to check the DC-3/DC-5 curves, which aren't listed here. The 1000 V DC maximum with two poles in series means this contactor handles high-voltage DC bus applications common in solar, battery storage, or traction systems. The 48-130 V AC/DC control voltage covers standard 48 V, 110 V, and 120 V control supplies — verify your panel's control voltage falls within the 0.8 to 1.1 times Uc operational limits. The B10d safety reliability level of 5 million cycles (per EN/ISO 13849-1) supports use in safety circuits where the contactor is mechanically loaded — relevant for emergency-stop or guard-door applications. ## Standards and compliance for the panel builder Certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, and CSA C22.2 No 60947-4-2. The overvoltage category is III, suitable for fixed-installation distribution panels. IP2X front-face protection with shrouds (per IEC 60529 and VDE 0106) means fingers are protected from live parts once the shrouds are fitted — standard for open-panel mounting on a plate. ## Mounting and wiring notes for the wireman Mounts on a plate (not DIN rail) with a 35 mm connection pitch. Power circuit connections accept busbars up to 25 x 6 mm, lugs/ring terminals up to 185 mm², or bolted connection. Control circuit uses push-in terminals for 0.2-2.5 mm² solid/stranded or 0.25-2.5 mm² flexible with ferrules. Tightening torque is 18 N.m on the power terminals.","metaTitle":"LC1G250DCEHEN TeSys Giga Contactor, 250 A DC-1, 48-130 V Coi","metaDescription":"TeSys Giga LC1G250DCEHEN DC contactor, 250 A rated operational current (DC-1), 48-130 V AC/DC coil. UL/CSA certified. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"193 mm","Range":"TeSys","Width":"108 mm","title":"LC1G250DCEHEN","Colour":"Dark grey","Height":"193 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 DIN 3852-Y CSA C22.2 No 60947-4-2","description":"High power contactor, TeSys Giga, 3P(3NO), DC-1 <=1500V 250A, 3 poles in series, 48...130V wideband AC/DC coil, for DC application,standard version","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Plate","Range of product":"TeSys Giga","Average impedance":"0.00017 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"18 N.m","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"DC-1","Contactor application":"Power switching","Mechanical durability":"1 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Associated fuse rating":"315 A aR at 1500 V for for DC 250 A aR at 1000 V for for DC","Maximum operating rate":"100 cyc/h DC-1","inrush power in W (DC)":"220 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 185 mm² Power circuit: bolted connection Control circuit: push-in 1 0.2...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25...2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5...1.0 mm² with cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"375 A at 1500 V for DC 3 poles in series 300 A at 1000 V for DC 2 poles in series","Pole contact composition":"3 NO","Safety reliability level":"B10d = 5000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"375 A at 1500 V DC for 3 poles in series 300 A at 1000 V DC for 2 poles in series","Power dissipation per pole":"10.7 W","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1500 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)","[Ie] rated operational current":"250 A (at 200 A (at <40 °C) DC-1 for 2 poles in series","[Ue] rated operational voltage":"<= 1000 V DC 2 poles in series","inrush power in VA (50/60 Hz, AC)":"290 VA","Ambient air temperature for storage":"-60...80 °C","hold-in power consumption in W (DC)":"5.7 W","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"12 kV","[Ith] conventional free air thermal current":"250 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ec1e9060ff46be9f90692b3c67df5f3.pdf","sourceUrl":"https://www.se.com/hk/en/product/LC1G250DCEHEN/high-power-contactor-tesys-giga-3p3no-dc1-1500v-250a-3-poles-in-series-48130v-wideband-ac-dc-coil-for-dc-applicationstandard-version/"},"ai":{"faq":[{"question":"What is the closest alternative in the TeSys Giga family?","answer":"Within the TeSys Giga range, the LC1G250DCEHEN is a 250 A DC-1 rated contactor. A lower-current sibling like the LC1G200DCEHEN (200 A DC-1) or higher-current LC1G300DCEHEN (300 A DC-1) would be the natural alternatives, but verify the coil voltage and pole configuration match your application."},{"question":"What compliance documentation is available?","answer":"The contactor is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, and CSA C22.2 No 60947-4-2. These standards cover the product safety and performance requirements for North American and European installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G250DCEHEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G250DCEHEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}