{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G2654LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G2654LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G2654LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G2654LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys Giga contactor, LC1G2654LSEN, 4-pole, 265 A AC-3, coil 200…500 V AC/DC, dark grey.","salesMarkdown":"The LC1G2654LSEN is a 4-pole power switching contactor from the TeSys Giga line, wired for AC-3 motor duty. The control circuit accepts 200…500 V AC or DC. Rated insulation voltage is 1000 V and the coil uses built-in bidirectional peak limiting. ## Fit & Installation Mounts on a plate (not direct DIN-rail—the Giga frame is bolt-down). Power terminals accept either busbars up to 32 × 10 mm or ring lugs up to 185 mm² per pole, with a pitch of 45 mm. Control circuit uses push-in connections for 0.2…2.5 mm² flexible wire. Auxiliary contacts are 1 NO + 1 NC, already built in. Tightening torque for the power terminations is 35 N·m—worth noting if you're using an impact driver; it's higher than a typical IEC contactor. The contactor meets EN/IEC 60947-4-1, UL 60947-4-1, CSA, and JIS, so it passes most panel approvals without extra paperwork.","metaTitle":"Schneider LC1G2654LSEN 4-Pole Contactor, 265A AC-3","metaDescription":"Active production TeSys Giga contactor rated 265 A AC-3, 4 NO poles, coil 200-500V AC/DC. Built-in peak limiting coil, 8 Mcycles mechanical durability. UL, IEC, CSA. RFQ for BOM fi","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"8.9 in (226 mm)","Range":"TeSys","Width":"7.3 in (185 mm)","title":"LC1G2654LSEN","Height":"8.9 in (225 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","description":"Contactor, high power, TeSys Giga, 4P(4NO), AC-1, <=440V 385A, standard version, 200-500V AC/DC wide band coil","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.8 in (45 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.000144 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"309.8 lbf.in (35 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"315 A aM at 250 A aM at 400 A gG at 450 A UL Type J at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"300 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2380 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"3320 A at 440 V","Power dissipation per pole":"20 W AC-1 - Ith 385 A 11 W AC-3 - Ith 265 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"265 A (at 385 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"530 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"9 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2.2 kA - 10 s 1.23 kA - 30 s 0.95 kA - 1 min 0.62 kA - 3 min 0.48 kA - 10 min","[Ith] conventional free air thermal current":"385 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9e668d3581d19775c7137864022d2fc4.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1G2654LSEN/contactor-high-power-tesys-giga-4p4no-ac1-440v-385a-standard-version-200500v-ac-dc-wide-band-coil/"},"ai":{"faq":[{"question":"What color is the LC1G2654LSEN?","answer":"Dark grey."},{"question":"What are its key electrical ratings?","answer":"Rated for 265 A AC-3 (motor duty), up to 385 A AC-1 (resistive). Control coil operates on 200…500 V AC 50/60 Hz or DC. Insulation voltage is 1000 V."},{"question":"What standards does the LC1G2654LSEN comply with?","answer":"EN/IEC 60947-4-1 and 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Also UL 60335-1 and UL 60335-2-40 for household appliance applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G2654LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G2654LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}