{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G330LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G330LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G330LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G330LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga series, LC1G330LSEN, 3-pole contactor, 330 A rated, 200-500 V AC/DC coil, motor power 90-220 kW depending on voltage.","salesMarkdown":"The Schneider Electric TeSys Giga LC1G330LSEN is a 3-pole power contactor rated for motor control and general power switching. Its 330 A thermal current (Ith) in AC-1 duty means it handles resistive loads at that current continuously; the real motor ratings depend on voltage and duty cycle. At 400 V AC 50/60 Hz in AC-3e duty it switches 160 kW, and at 690 V it reaches 220 kW. The 200-500 V AC/DC control coil includes built-in bidirectional peak limiting, so you don't need an external varistor or RC snubber for coil suppression. ## Standards and compliance — what the approvals mean This contactor carries dual certification to EN/IEC 60947-4-1 and UL 60947-4-1, which means it is accepted for motor-controller duty in both IEC and North American panels. It also meets CSA C22.2 No 60947-4-1 for Canadian installations and JIS C8201-4-1 for Japanese markets. The additional IEC 60335-1 and UL 60335-2-40 listings cover its use in HVAC equipment — specifically heat-pump and refrigeration circuits where the contactor must pass the glow-wire and abnormal-operation tests of those appliance standards. Mounting is plate-mount only — no DIN-rail clip on this frame size. Power terminals accept bar (32 x 10 mm max), lugs up to 185 mm², or bolted connections. Tightening torque for power connections is 35 N·m. The front face with shrouds provides IP2X finger protection per IEC 60529 and VDE 0106. ## Mechanical and electrical endurance Maximum operating rate is 600 cycles per hour in AC-3 or AC-3e duty, dropping to 150 cycles per hour in AC-4 (plugging/reversing). The B10d safety reliability figures are 400,000 cycles at nominal load and 3,000,000 cycles at mechanical load per EN/ISO 13849-1, which supports its use in safety-related control circuits where contactor failure must be predictable. ## Fault current coordination Rated making capacity is 3830 A at 440 V; breaking capacity is 2940 A at 440 V. Associated fuse recommendations are 400 A aM, 250 A aM, 500 A gG, or 600 A UL Type L at up to 600 V — these are the fuse sizes for Type 2 coordination (no damage to the contactor under short-circuit). For a 480 V panel in North America, the 250 hp rating at 460/480 V 60 Hz gives the motor nameplate limit.","metaTitle":"Schneider TeSys Giga LC1G330LSEN Contactor, 330 A, 3P, 200-5","metaDescription":"Schneider Electric TeSys Giga LC1G330LSEN contactor. 330 A rated, 3-pole, 200-500 V AC/DC coil. Motor power up to 220 kW at 690 V. UL/CSA/IEC listed. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"8.9 in (226 mm)","Range":"TeSys","Width":"5.5 in (140 mm)","title":"LC1G330LSEN","Height":"8.9 in (225 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","description":"High power contactor,TeSys Giga,3P(3NO),AC-3 <=440V 330A,standard version,200-500V AC/DC wide band coil","Motor power kW":"90 kW at 230 V AC 50/60 Hz (AC-3e) 160 kW at 400 V AC 50/60 Hz (AC-3e) 160 kW at 415 V AC 50/60 Hz (AC-3e) 185 kW at 440 V AC 50/60 Hz (AC-3e) 200 kW at 500 V AC 50/60 Hz (AC-3e) 220 kW at 690 V AC 50/60 Hz (AC-3e) 185 kW at 1000 V AC 50/60 Hz (AC-3e) 90 kW at 230 V AC 50/60 Hz (AC-3) 160 kW at 400 V AC 50/60 Hz (AC-3) 160 kW at 415 V AC 50/60 Hz (AC-3) 200 kW at 440 V AC 50/60 Hz (AC-3) 200 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 90 kW at 230 V AC 50/60 Hz (AC-4) 160 kW at 400 V AC 50/60 Hz (AC-4) 160 kW at 415 V AC 50/60 Hz (AC-4) 185 kW at 440 V AC 50/60 Hz (AC-4) 200 kW at 500 V AC 50/60 Hz (AC-4) 220 kW at 690 V AC 50/60 Hz (AC-4) 185 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.8 in (45 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.000144 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"309.8 lbf.in (35 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"400 A aM at 250 A aM at 500 A gG at 600 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"300 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"2940 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"3830 A at 440 V","Maximum Horse Power Rating":"100 hp at 200/208 V 60 Hz 125 hp at 230/240 V 60 Hz 250 hp at 460/480 V 60 Hz 300 hp at 575/600 V 60 Hz","Power dissipation per pole":"30 W AC-1 - Ith 440 A 16 W AC-3 - Ith 330 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"440 A (at 330 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"530 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"9 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2.65 kA - 10 s 1.8 kA - 30 s 1.3 kA - 1 min 0.9 kA - 3 min 0.75 kA - 10 min","[Ith] conventional free air thermal current":"440 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,720.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c7ed06c7ae4702be2d968e252373861.pdf","sourceUrl":"https://www.se.com/ca/en/product/LC1G330LSEN/high-power-contactortesys-giga3p3noac3-440v-330astandard-version200500v-ac-dc-wide-band-coil/"},"ai":{"faq":[{"question":"What is the closest alternative to the LC1G330LSEN in the TeSys family?","answer":"Within the TeSys Giga range, the LC1G330LSEN is a specific coil-voltage variant (200-500 V AC/DC). The same frame with a different coil voltage — for example, a 110-120 V AC coil variant — is the same physical contactor but with a different control circuit. The deciding factor is your panel's control voltage; if your system uses 230 V control, this exact variant fits. There is no pin-compatible substitute from a different series that matches the 330 A frame and the same mounting footprint."},{"question":"What color is the LC1G330LSEN?","answer":"Dark grey."},{"question":"What is the depth of the LC1G330LSEN?","answer":"8.9 inches (226 mm)."},{"question":"What compliance documentation does Schneider provide for this contactor?","answer":"The LC1G330LSEN is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and JIS C8201-5-1. It also carries IEC 60335-1 and UL 60335-2-40 appliance-standard listings. The protective treatment is TH (tropicalized/humid environment). A RoHS/REACH declaration of conformity is standard for Schneider TeSys Giga products."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G330LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G330LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}