{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G4004EHEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G4004EHEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G4004EHEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G4004EHEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G4004EHEN 4-pole contactor, 48-130V AC/DC coil, 1000V insulation voltage, 8 Mcycles mechanical durability.","salesMarkdown":"The LC1G4004EHEN is a 4-pole contactor from the TeSys Giga range, rated for 1000 V insulation voltage and switching loads across AC-3, AC-3e, AC-1, AC-5a/b, AC-6a/b utilization categories, with a bidirectional peak limiting coil accepting 48…130 V AC/DC. Mechanical durability is 8 Mcycles, maximum operating rate 600 cyc/h and 300 cyc/h. Power dissipation per pole is 30 W at 550 A and 16 W at 400 A. The contactor is certified to EN/IEC 60947-4-1 and -5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1 and -5-1, plus UL 60335-1 and UL 60335-2-40 Annex JJ for appliance applications. Overvoltage category III, protective treatment TH (humid/ambient). Safety reliability numbers are provided: B10d 400,000 cycles under nominal electrical load, 3,000,000 cycles under purely mechanical load. ## Termination and Mounting Power connections accept bar/busbar up to 32×10 mm or ring lugs up to 185 mm².","metaTitle":"Schneider TeSys Giga LC1G4004EHEN 4-Pole Contactor, 48-130V","metaDescription":"Active-production 4-pole contactor by Schneider Electric. 1000V rated insulation, 48-130V AC/DC coil, AC-3/AC-1 utilization. Full traceability through authorized channel. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"8.9 in (226 mm)","Range":"TeSys","Width":"7.3 in (185 mm)","Height":"8.9 in (225 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.8 in (45 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.0001 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"309.8 lbf.in (35 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"760 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"3480 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"5090 A at 440 V","Power dissipation per pole":"30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"400 A (at 550 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"965 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"7.8 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min","[Ith] conventional free air thermal current":"550 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,395.00 – $2,554.81","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42d25c6bb464ca1bf2de17e561b42a53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G4004EHEN/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings of the LC1G4004EHEN?","answer":"Rated insulation voltage 1000 V; coil operates on 48-130 V AC 50/60 Hz or 48-130 V DC; utilization categories include AC-3 (motor), AC-1 (resistive), and DC switching; mechanical durability 8 million cycles; power dissipation per pole 30 W at AC-1 and 16 W at AC-3."},{"question":"What compliance certifications does this contactor carry?","answer":"It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40 Annex JJ. Overvoltage category III, protective treatment TH."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G4004EHEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G4004EHEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}