{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G4004EHES207N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G4004EHES207N","canonicalUrl":"https://aoctrl.com/schneider/LC1G4004EHES207N","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G4004EHES207N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga series, 4-pole contactor LC1G4004EHES207N, 200 kW at 400 V AC-3e, 48-130 V AC/DC coil, plate mount.","salesMarkdown":"The LC1G4004EHES207N is a 4-pole TeSys Giga contactor rated for 200 kW at 400 V AC-3e — that is the motor-switching duty class that governs real-world induction motor starts and stops. The AC-3e rating, not the higher AC-1 resistive current, is the one that decides whether this contactor holds in on a compressor or conveyor drive. At 460/480 V 60 Hz it handles 300 hp, and at 575/600 V 60 Hz it handles 400 hp, which covers most North American medium-voltage motor frames in a single device. The control circuit accepts 48-130 V AC or DC, with a built-in bidirectional peak-limiting coil that suppresses the inductive kick on dropout. That means no external varistor or RC snubber needed across the coil terminals — one less component to source and mount on the panel rail. Rated insulation voltage is 1000 V, and the contactor carries overvoltage category III, so it is suited for fixed-installation distribution panels where transient overvoltages from the supply side are expected. ## Deployment context This contactor mounts on a plate — not a DIN rail — so plan for a drilled backplate in the enclosure. The power circuit uses bolted connections: bar or busbar up to 32 x 10 mm, or lugs up to 185 mm². Tightening torque on the main connections is 35 N·m, which requires a torque wrench during panel assembly. The 225 mm cube footprint (225 x 140 x 225 mm) and 45 mm pole pitch mean it occupies a significant chunk of backplate real estate — factor that into gland-plate planning and cable bend radius for the 185 mm² power conductors. Compliance documentation is extensive: the contactor is certified to EN/IEC 60947-4-1 (contactor standard), EN/IEC 60947-5-1 (control circuit devices), UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and JIS C8201-5-1. It also carries UL 60335-1 and UL 60335-2-40 Annex JJ for household and HVAC appliance applications. The TH protective treatment indicates it is suitable for tropical/humid environments. ## Safety and durability The safety reliability figures (B10d = 400,000 cycles at nominal load, 3,000,000 cycles at mechanical load per EN/ISO 13849-1) mean it can be used in safety-related control circuits where the contactor is part of the stopping chain. Vibration resistance is 2 gn (contact open) and 4 gn (contact closed) across 5-300 Hz, with shock resistance of 10 gn (open) and 15 gn (closed) at 11 ms. That is sufficient for most industrial environments including near large rotating machinery.","metaTitle":"Schneider Electric LC1G4004EHES207N TeSys Giga Contactor, 4P","metaDescription":"TeSys Giga 4-pole contactor, 200 kW at 400 V AC-3e, 48-130 V AC/DC coil, UL/CSA/IEC rated. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"225 mm","Range":"TeSys","Width":"140 mm","Colour":"Dark grey","Height":"225 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","Motor power hp":"125 hp at 200/208 V 60 Hz 150 hp at 230/240 V 60 Hz 300 hp at 460/480 V 60 Hz 400 hp at 575/600 V 60 Hz","Motor power kW":"110 kW at 230 V AC 50/60 Hz (AC-3e) 200 kW at 400 V AC 50/60 Hz (AC-3e) 200 kW at 415 V AC 50/60 Hz (AC-3e) 250 kW at 440 V AC 50/60 Hz (AC-3e) 250 kW at 500 V AC 50/60 Hz (AC-3e) 315 kW at 690 V AC 50/60 Hz (AC-3e) 220 kW at 1000 V AC 50/60 Hz (AC-3e) 110 kW at 230 V AC 50/60 Hz (AC-3) 200 kW at 400 V AC 50/60 Hz (AC-3) 200 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 500 V AC 50/60 Hz (AC-3) 315 kW at 690 V AC 50/60 Hz (AC-3) 220 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 230 V AC 50/60 Hz (AC-4) 200 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 415 V AC 50/60 Hz (AC-4) 220 kW at 440 V AC 50/60 Hz (AC-4) 250 kW at 500 V AC 50/60 Hz (AC-4) 315 kW at 690 V AC 50/60 Hz (AC-4) 220 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"45 mm","Mounting support":"Plate","Range of product":"TeSys Giga","Average impedance":"0.0001 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"35 N.m","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Associated fuse rating":"500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V","Maximum operating rate":"300 cyc/h AC-1 500 cyc/h AC-3 500 cyc/h AC-3e 150 cyc/h AC-4","inrush power in W (DC)":"760 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 185 mm² Power circuit: bolted connection Control circuit: push-in 1 0.2...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25...2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5...1.0 mm² with cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"3480 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"5090 A at 440 V","Power dissipation per pole":"30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)","[Ie] rated operational current":"550 A (at 400 A (at <60 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"965 VA","Ambient air temperature for storage":"-60...80 °C","hold-in power consumption in W (DC)":"7.8 W","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min","[Ith] conventional free air thermal current":"550 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42d25c6bb464ca1bf2de17e561b42a53.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1G4004EHES207N/high-power-contactortesys-giga-s2074p4noac3-440v-400astandard-version48130v-ac-dc-wide-band-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G4004EHES207N/alternatives.json"},"ai":{"faq":[{"question":"What compliance certifications does this contactor carry?","answer":"It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40 Annex JJ. The TH protective treatment qualifies it for tropical environments."},{"question":"What is the rated motor power at 400 V AC?","answer":"200 kW at 400 V AC in both AC-3e and AC-4 duty classes. At 460/480 V 60 Hz it is rated for 300 hp, and at 575/600 V 60 Hz for 400 hp."},{"question":"What is the control coil voltage range?","answer":"48-130 V AC 50/60 Hz and 48-130 V DC, with built-in bidirectional peak limiting — no external suppression needed."},{"question":"How does this compare to a standard TeSys contactor?","answer":"The TeSys Giga series is the heavy-duty, high-current platform compared to the TeSys D or F ranges. This 4-pole unit handles up to 315 kW at 690 V AC-3e and 400 hp at 575-600 V, with bolted power connections and 8 Mcycles mechanical life — it is sized for large motor control centers and high-duty-cycle applications, not light panel duty."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G4004EHES207N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G4004EHES207N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}