{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G400EHEA","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G400EHEA","canonicalUrl":"https://aoctrl.com/schneider/LC1G400EHEA","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G400EHEA","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G400EHEA 3-pole contactor, 48-130 V AC/DC coil, built-in peak limiting, 200 kW at 400 V AC-3e, 8 Mcycles.","salesMarkdown":"## Schneider Electric TeSys Giga LC1G400EHEA The LC1G400EHEA is a three-pole TeSys Giga contactor from Schneider Electric, rated for power switching and motor control across AC-3e, AC-3, and AC-4 duty cycles. Coil accepts 48–130 V AC or DC (50/60 Hz), with built-in bidirectional peak limiting — no external suppressor needed. Check polarity if retrofitting into a panel with existing suppression, but this unit handles its own noise. Mechanical durability is rated at 8 million cycles; operating time is 40–70 ms closing, 15–50 ms opening. For 400 V mains, motor power capability reaches 200 kW in AC-3e duty; rated breaking capacity is 3480 A at 440 V, making capacity 5090 A. Auxiliary contacts are 1 NO + 1 NC, integrated into the molded housing. Dimensions: 226 mm deep, 140 mm wide, 290 mm high. Mounts to a plate; power terminals accept bar, busbar, or ring lugs up to 185 mm². Complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS standards. Front face achieves IP2X with shrouds.","metaTitle":"Schneider LC1G400EHEA TeSys Giga Contactor, 48-130V Coil","metaDescription":"Active TeSys Giga 3-pole contactor. Coil 48-130V AC/DC with built-in peak limiting. Rated 200 kW at 400V AC-3e. 8 Mcycles mechanical. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"8.9 in (226 mm)","Range":"TeSys","Width":"5.5 in (140 mm)","Height":"11.4 in (290 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","Motor power kW":"110 kW at 230 V AC 50/60 Hz (AC-3e) 200 kW at 400 V AC 50/60 Hz (AC-3e) 200 kW at 415 V AC 50/60 Hz (AC-3e) 250 kW at 440 V AC 50/60 Hz (AC-3e) 250 kW at 500 V AC 50/60 Hz (AC-3e) 315 kW at 690 V AC 50/60 Hz (AC-3e) 220 kW at 1000 V AC 50/60 Hz (AC-3e) 110 kW at 230 V AC 50/60 Hz (AC-3) 200 kW at 400 V AC 50/60 Hz (AC-3) 200 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 500 V AC 50/60 Hz (AC-3) 315 kW at 690 V AC 50/60 Hz (AC-3) 220 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 230 V AC 50/60 Hz (AC-4) 200 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 415 V AC 50/60 Hz (AC-4) 220 kW at 440 V AC 50/60 Hz (AC-4) 250 kW at 500 V AC 50/60 Hz (AC-4) 315 kW at 690 V AC 50/60 Hz (AC-4) 220 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.8 in (45 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.0001 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"309.8 lbf.in (35 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"360 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"3480 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"5090 A at 440 V","Maximum Horse Power Rating":"125 hp at 200/208 V 60 Hz 150 hp at 230/240 V 60 Hz 300 hp at 460/480 V 60 Hz 400 hp at 575/600 V 60 Hz","Power dissipation per pole":"30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"550 A (at 400 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"450 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"8.3 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min","[Ith] conventional free air thermal current":"550 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,120.00 – $2,457.47","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42d25c6bb464ca1bf2de17e561b42a53.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G400EHEA/alternatives.json"},"ai":{"faq":[{"question":"What is the color of the LC1G400EHEA?","answer":"Dark grey."},{"question":"What is the depth of the LC1G400EHEA?","answer":"226 mm (8.9 in)."},{"question":"What compliance standards does it meet?","answer":"It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and JIS C8201-5-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G400EHEA","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G400EHEA when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}