{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G400XXEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G400XXEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G400XXEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G400XXEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga series, LC1G400XXEN, 3-pole contactor, 315 kW at 690 V AC-3e, 8 Mcycles mechanical durability, IP2X front face.","salesMarkdown":"## Motor ratings and utilisation categories In AC-3e duty it switches 315 kW at 690 V AC 50/60 Hz, and 220 kW at 1000 V AC. At 400 V AC the rating is 200 kW. These figures cover the common industrial voltages for pump, fan, and compressor loads. The utilisation categories listed include AC-1 through AC-8b plus DC-1, DC-3, and DC-5, so the contactor handles resistive heating, motor starting, and DC switching without derating concerns. Certified to EN/IEC 60947-4-1 and EN/IEC 60947-5-1, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. Also carries JIS C8201-4-1 and JIS C8201-5-1 for Japanese markets. Overvoltage category III. The front face with shrouds achieves IP2X per IEC 60529 and VDE 0106. Listed as current lifecycle stage. No official successor has been published. For BOM freeze or PCN watch, the compliance documentation set includes the standards listed above; RoHS and REACH declarations are available on request with the RFQ. ## Mechanical and electrical endurance Rated for 8 Mcycles mechanical durability. Maximum operating rate is 600 cycles/hour in AC-3 and AC-3e, 300 cycles/hour in AC-1, and 150 cycles/hour in AC-4. Inrush power at DC is 350 W. ## Connection and mounting Power circuit connections accept bar or busbar cross-section up to 32 x 10 mm, or lugs-ring terminals for 185 mm² cable. Tightening torque for power connections is 35 N.m. Mounting is plate-mount with a connection pitch of 45 mm. The dark grey housing measures 226 mm deep, 140 mm wide, and 225 mm high.","metaTitle":"Schneider TeSys Giga LC1G400XXEN Contactor, 315 kW at 690 V","metaDescription":"Schneider TeSys Giga LC1G400XXEN 3-pole contactor. 315 kW at 690 V AC-3e. Current lifecycle stage. Sourced to order against RFQ. UL/CSA/IEC certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"8.9 in (226 mm)","Range":"TeSys","Width":"5.5 in (140 mm)","title":"LC1G400XXEN","Height":"8.9 in (225 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1","description":"High power contactor,TeSys Giga,3P(3NO),AC-3 <=440V 400A,standard version,600V AC/DC coil","Motor power kW":"110 kW at 230 V AC 50/60 Hz (AC-3e) 200 kW at 400 V AC 50/60 Hz (AC-3e) 200 kW at 415 V AC 50/60 Hz (AC-3e) 250 kW at 440 V AC 50/60 Hz (AC-3e) 250 kW at 500 V AC 50/60 Hz (AC-3e) 315 kW at 690 V AC 50/60 Hz (AC-3e) 220 kW at 1000 V AC 50/60 Hz (AC-3e) 110 kW at 230 V AC 50/60 Hz (AC-3) 200 kW at 400 V AC 50/60 Hz (AC-3) 200 kW at 415 V AC 50/60 Hz (AC-3) 250 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 500 V AC 50/60 Hz (AC-3) 315 kW at 690 V AC 50/60 Hz (AC-3) 220 kW at 1000 V AC 50/60 Hz (AC-3) 110 kW at 230 V AC 50/60 Hz (AC-4) 200 kW at 400 V AC 50/60 Hz (AC-4) 200 kW at 415 V AC 50/60 Hz (AC-4) 220 kW at 440 V AC 50/60 Hz (AC-4) 250 kW at 500 V AC 50/60 Hz (AC-4) 315 kW at 690 V AC 50/60 Hz (AC-4) 220 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"1.8 in (45 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.0001 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"309.8 lbf.in (35 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"8 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"500 A aM at 315 A aM at 630 A gG at 600 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"350 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"3480 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"5090 A at 440 V","Maximum Horse Power Rating":"125 hp at 200/208 V 60 Hz 150 hp at 230/240 V 60 Hz 300 hp at 460/480 V 60 Hz 400 hp at 575/600 V 60 Hz","Power dissipation per pole":"30 W AC-1 - Ith 550 A 16 W AC-3 - Ith 400 A","[Uc] control circuit voltage":"600 V AC 50/60 Hz 600 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"550 A (at 400 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"550 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"9 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3.6 kA - 10 s 2.4 kA - 30 s 1.7 kA - 1 min 1.2 kA - 3 min 1.0 kA - 10 min","[Ith] conventional free air thermal current":"550 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,880.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23f99527c4993fb2fb16ff88c9c0a8bd.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1G400XXEN/high-power-contactortesys-giga3p3noac3-440v-400astandard-version600v-ac-dc-coil/"},"ai":{"faq":[{"question":"What motor power does it handle at 690 V?","answer":"In AC-3e duty it switches 315 kW at 690 V AC 50/60 Hz. At 400 V AC the rating is 200 kW."},{"question":"What compliance certifications does it carry?","answer":"Certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1 / JIS C8201-5-1."},{"question":"What is the mechanical durability rating?","answer":"Rated for 8 million mechanical cycles. Maximum operating rate is 600 cycles/hour in AC-3 duty."},{"question":"What wire sizes does the control circuit accept?","answer":"Push-in terminals accept 0.2 to 2.5 mm² solid or stranded wire with ferrule, or 0.5 to 1.0 mm² with cable end."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G400XXEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G400XXEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}