{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G630EHES207N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G630EHES207N","canonicalUrl":"https://aoctrl.com/schneider/LC1G630EHES207N","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G630EHES207N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga, LC1G630EHES207N, 3-pole contactor, 630 A AC-3e, 48-130 V AC/DC coil, 315 kW at 400 V.","salesMarkdown":"The LC1G630EHES207N is a 3-pole TeSys Giga contactor rated for 630 A in AC-3e duty. The AC-3e category (enhanced AC-3 per IEC 60947-4-1) means it is tested for the higher electrical endurance demanded by modern variable-speed drive inputs and frequent motor starts. The control circuit accepts 48-130 V AC/DC with built-in bidirectional peak limiting, so you do not need an external varistor or RC snubber across the coil. Drop-out is guaranteed between 0.1 and 0.45 Uc below 60 °C — useful to know if your control supply is shared with PLC outputs that sag during inrush. Mechanical durability is rated at 5 million cycles, and the B10d safety reliability figure is 100,000 cycles at nominal load per EN/ISO 13849-1. That puts it in the range for safety circuits where the contactor is part of a monitored stop chain, not just general power switching. This contactor class sits inside motor control centres and large panel builds for pumps, conveyors, compressors, and HVAC fans. The plate-mount format and 70 mm connection pitch suit bolted busbar systems typical in 600+ A switchgear. The IP2X front face with shrouds meets touch-safe requirements per IEC 60529 and VDE 0106. ## Integration notes Mounting is plate-only — no DIN rail clip for this frame. Tightening torque for the power connections is 58 N·m. The 266 mm depth and 284 mm height need to be checked against enclosure gland-plate clearance and busbar rise. Power dissipation per pole is 70 W at AC-1 (Ith 1050 A) and 26 W at AC-3 (Ith 630 A). That heat has to be factored into panel ventilation — at full AC-3 load the three poles together dump 78 W into the enclosure.","metaTitle":"Schneider TeSys Giga LC1G630EHES207N Contactor, 630 A AC-3e,","metaDescription":"Schneider Electric TeSys Giga LC1G630EHES207N 3-pole contactor. 630 A AC-3e, 48-130 V AC/DC coil. 315 kW at 400 V. EN/IEC/UL/CSA. Current lifecycle. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"266 mm","Range":"TeSys","Width":"211 mm","Colour":"Dark grey","Height":"284 mm","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","Motor power hp":"250 hp at 200/208 V 60 Hz 300 hp at 230/240 V 60 Hz 600 hp at 460/480 V 60 Hz 700 hp at 575/600 V 60 Hz","Motor power kW":"180 kW at 230 V AC 50/60 Hz (AC-3e) 315 kW at 400 V AC 50/60 Hz (AC-3e) 335 kW at 415 V AC 50/60 Hz (AC-3e) 355 kW at 440 V AC 50/60 Hz (AC-3e) 375 kW at 500 V AC 50/60 Hz (AC-3e) 500 kW at 690 V AC 50/60 Hz (AC-3e) 450 kW at 1000 V AC 50/60 Hz (AC-3e) 200 kW at 230 V AC 50/60 Hz (AC-3) 335 kW at 400 V AC 50/60 Hz (AC-3) 375 kW at 415 V AC 50/60 Hz (AC-3) 400 kW at 440 V AC 50/60 Hz (AC-3) 400 kW at 500 V AC 50/60 Hz (AC-3) 500 kW at 690 V AC 50/60 Hz (AC-3) 450 kW at 1000 V AC 50/60 Hz (AC-3) 180 kW at 230 V AC 50/60 Hz (AC-4) 315 kW at 400 V AC 50/60 Hz (AC-4) 335 kW at 415 V AC 50/60 Hz (AC-4) 355 kW at 440 V AC 50/60 Hz (AC-4) 375 kW at 500 V AC 50/60 Hz (AC-4) 450 kW at 690 V AC 50/60 Hz (AC-4) 355 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"70 mm","Mounting support":"Plate","Range of product":"TeSys Giga","Average impedance":"0.000065 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"58 N.m","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"5 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Associated fuse rating":"630 A aM at 500 A aM at 1250 A gG at 1000 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"790 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 52 x 20 mm Power circuit: lugs-ring terminals 1 185 mm² Power circuit: bolted connection Control circuit: push-in 1 0.2...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25...2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5...1.0 mm² with cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75...2.5 mm² - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106","Rated breaking capacity":"5550 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 100000 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 1800000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"7220 A at 440 V","Power dissipation per pole":"70 W AC-1 - Ith 1050 A 26 W AC-3 - Ith 630 A","[Uc] control circuit voltage":"48...130 V AC 50/60 Hz 48...130 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)","[Ie] rated operational current":"1050 A (at 630 A (at <60 °C) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"990 VA","Ambient air temperature for storage":"-60...80 °C","hold-in power consumption in W (DC)":"9.5 W","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"5.05 kA - 10 s 4.4 kA - 30 s 3.4 kA - 1 min 2.2 kA - 3 min 1.6 kA - 10 min","[Ith] conventional free air thermal current":"1050 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/LC1G630EHES207N/high-power-contactortesys-giga-s2073p3noac3-440v-630astandard-version48130v-ac-dc-wide-band-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1G630EHES207N/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor power ratings?","answer":"At 400 V AC 50/60 Hz in AC-3e duty it switches 315 kW. At 460/480 V 60 Hz the motor power is 600 hp. Full ratings across AC-3, AC-3e, and AC-4 categories are listed for voltages from 230 V to 1000 V."},{"question":"What standards does this contactor comply with?","answer":"It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and JIS C8201-5-1, plus the appliance standards IEC 60335-1 Clause 30.2 and UL 60335-1."},{"question":"What is the control voltage range?","answer":"The coil accepts 48-130 V AC 50/60 Hz and 48-130 V DC. Built-in bidirectional peak limiting handles coil suppression internally."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G630EHES207N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G630EHES207N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}