{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G630LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G630LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G630LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G630LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga, 3-pole contactor, 630 A, 315 kW at 400 V AC-3e, coil 200...500 V AC/DC, plate mount.","salesMarkdown":"The contactor is rated across multiple utilisation categories including AC-1 (resistive), AC-3/AC-3e (squirrel-cage motor starting), AC-4 (plugging/inching), and DC-1/DC-3/DC-5 for DC loads. This breadth means it can serve as a single part number across diverse load types in a panel, reducing BOM complexity. The 630 A rating in AC-1 (resistive) duty is the thermal current the main poles can carry continuously. The AC-4 rating of 315 kW at 400 V covers the more severe reversing or jogging duty, where the contacts must make and break locked-rotor current. For North American installations, the horsepower ratings are 600 hp at 460/480 V 60 Hz and 700 hp at 575/600 V 60 Hz. The mechanical durability is 5 million cycles, and the maximum operating rate is 600 cycles/hour for AC-3/AC-3e duty, 300 for AC-1, and 150 for AC-4. These figures set the service life and switching frequency limits for automated applications like conveyor systems or pump cycling. Additional compliance with IEC 60335-1 Clause 30.2 and UL 60335-2-40 Annex JJ covers its use in appliance and HVAC applications where glow-wire and flammability testing is required. ## Integration notes The contactor mounts to a plate (not DIN rail) with a connection pitch of 70 mm between phases. Power connections accept bar or busbar cross-sections up to 52 x 20 mm, or lugs/ring terminals for 185 mm² cable. Tightening torque for the main connections is 58 N·m. The front face achieves IP2X with shrouds fitted. The auxiliary contact block is factory-fitted with 1 NO + 1 NC configuration. For applications requiring additional signalling or interlocking, the TeSys Giga range offers plug-in auxiliary blocks that share the same mounting footprint.","metaTitle":"Schneider Electric LC1G630LSEN TeSys Giga Contactor, 630 A,","metaDescription":"Schneider Electric LC1G630LSEN TeSys Giga 3-pole contactor. Rated 630 A, 315 kW at 400 V AC-3e. Coil 200-500 V AC/DC. UL/CSA/IEC. Active production. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"10.5 in (266 mm)","Range":"TeSys","Width":"8.3 in (211 mm)","title":"LC1G630LSEN","Height":"11.2 in (284 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ","description":"High power contactor,TeSys Giga,3P(3NO),AC-3 <=440V 630A,standard version,200-500V AC/DC wide band coil","Motor power kW":"180 kW at 230 V AC 50/60 Hz (AC-3e) 315 kW at 400 V AC 50/60 Hz (AC-3e) 335 kW at 415 V AC 50/60 Hz (AC-3e) 355 kW at 440 V AC 50/60 Hz (AC-3e) 375 kW at 500 V AC 50/60 Hz (AC-3e) 500 kW at 690 V AC 50/60 Hz (AC-3e) 450 kW at 1000 V AC 50/60 Hz (AC-3e) 200 kW at 230 V AC 50/60 Hz (AC-3) 335 kW at 400 V AC 50/60 Hz (AC-3) 375 kW at 415 V AC 50/60 Hz (AC-3) 400 kW at 440 V AC 50/60 Hz (AC-3) 400 kW at 500 V AC 50/60 Hz (AC-3) 500 kW at 690 V AC 50/60 Hz (AC-3) 450 kW at 1000 V AC 50/60 Hz (AC-3) 180 kW at 230 V AC 50/60 Hz (AC-4) 315 kW at 400 V AC 50/60 Hz (AC-4) 335 kW at 415 V AC 50/60 Hz (AC-4) 355 kW at 440 V AC 50/60 Hz (AC-4) 375 kW at 500 V AC 50/60 Hz (AC-4) 450 kW at 690 V AC 50/60 Hz (AC-4) 355 kW at 1000 V AC 50/60 Hz (AC-4)","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"2.8 in (70 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.000065 Ohm","Device short name":"LC1G","Poles description":"3P","Tightening torque":"513.3 lbf.in (58 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5","Contactor application":"Power switching Motor control","Mechanical durability":"5 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"630 A aM at 500 A aM at 1250 A gG at 1000 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4","inrush power in W (DC)":"390 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 52 x 20 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"5550 A at 440 V","Pole contact composition":"3 NO","Safety reliability level":"B10d = 100000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 1800000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"7220 A at 440 V","Maximum Horse Power Rating":"250 hp at 200/208 V 60 Hz 300 hp at 230/240 V 60 Hz 600 hp at 460/480 V 60 Hz 700 hp at 575/600 V 60 Hz","Power dissipation per pole":"70 W AC-1 - Ith 1050 A 26 W AC-3 - Ith 630 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"1050 A (at 630 A (at <140 °F (60 °C)) at <= 440 V AC-3","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"670 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"11 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"5.05 kA - 10 s 4.4 kA - 30 s 3.4 kA - 1 min 2.2 kA - 3 min 1.6 kA - 10 min","[Ith] conventional free air thermal current":"1050 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,950.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/93732a1129332f787a2e53843494ec0d.pdf","sourceUrl":"https://www.se.com/ca/en/product/LC1G630LSEN/high-power-contactortesys-giga3p3noac3-440v-630astandard-version200500v-ac-dc-wide-band-coil/"},"ai":{"faq":[{"question":"What are the key motor power ratings for this contactor?","answer":"At 400 V AC 50/60 Hz, the motor power is 315 kW in AC-3e duty and 315 kW in AC-4 duty. For North American voltages, it is rated 600 hp at 460/480 V 60 Hz and 700 hp at 575/600 V 60 Hz."},{"question":"What standards does the LC1G630LSEN comply with?","answer":"It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, IEC 60335-1 Clause 30.2, IEC 60335-2-40 Annex JJ, UL 60335-1, and UL 60335-2-40 Annex JJ."},{"question":"What is the control coil voltage range?","answer":"The coil accepts 200...500 V AC 50/60 Hz and 200...500 V DC, with built-in bidirectional peak limiting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G630LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G630LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}