{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1G8004LSEN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1G8004LSEN","canonicalUrl":"https://aoctrl.com/schneider/LC1G8004LSEN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1G8004LSEN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Giga LC1G8004LSEN, 4-pole contactor, 800 A rated, coil 200...500 V AC/DC, plate mount, dark grey.","salesMarkdown":"Utilisation categories cover AC-3 (squirrel-cage motor starting), AC-3e (high-efficiency motor starting), AC-1 (resistive loads), plus DC-1/DC-3/DC-5 for DC switching. The AC-3 rating is the one that governs most motor applications — this contactor is sized for 800 A in AC-3 duty, so it handles a 400–500 kW motor at 400 V without derating. Power dissipation per pole sits at 70 W in AC-1 at 1050 A and 42 W in AC-3 at 800 A. Associated fuse ratings are 800 A aM or 1250 A gG — the aM curve protects against motor start surges while the gG curve covers general fault clearing. For UL installations, a Type L fuse at ≤600 V is listed. Mechanical durability is 5 million cycles, with maximum operating rates of 600 cycles/hour in AC-3 and 300 cycles/hour in AC-1. That suits high-speed material handling or conveyor applications where the contactor cycles frequently. ## Mounting and connection Plate-mounted only (no DIN-rail option on this frame). The power terminals accept busbars up to 52 x 20 mm or ring lugs for 185 mm² cable. Tightening torque is 58 N·m on the power connections — a torque wrench is expected. Dimensions: 11.2 in (284 mm) high, 11.06 in (281 mm) wide, 10.5 in (266 mm) deep. The 70 mm connection pitch between poles matches the TeSys Giga busbar system. IP2X protection on the front face with shrouds installed. The protective treatment (TH) indicates the contactor is tropicalized for high-humidity environments — a detail worth noting if the panel sits in an unconditioned plant area.","metaTitle":"Schneider TeSys Giga LC1G8004LSEN Contactor, 4P, AC/DC Coil","metaDescription":"TeSys Giga LC1G8004LSEN 4-pole contactor, 800 A rating, 200-500 V AC/DC coil. AC-3/AC-1 switching, 1000 V insulation, UL/CSA/IEC certified. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Color":"Dark grey","Depth":"10.5 in (266 mm)","Range":"TeSys","Width":"11.06 in (281 mm)","title":"LC1G8004LSEN","Height":"11.2 in (284 mm)","Category":"US10I1222329","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ","description":"Contactor, high power, TeSys Giga, 4P(4NO), AC-1, <=440V 1050A, standard version, 200-500V AC/DC wide band coil, 800A frame","Operating time":"40...70 ms closing 15...50 ms opening","Coil technology":"Built-in bidirectional peak limiting","lifecycle_stage":"current","Connection pitch":"2.8 in (70 mm)","Mounting Support":"Plate","Range of Product":"TeSys Giga","Average impedance":"0.000065 Ohm","Device short name":"LC1G","Poles description":"4P","Tightening torque":"513.3 lbf.in (58 N.m)","Compatibility code":"LC1G","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5","Contactor application":"Power switching","Mechanical durability":"5 Mcycles","Mechanical robustness":"Vibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed","Nbr. of units in pkg.":"1","Associated fuse rating":"800 A aM at 630 A aM at 1250 A gG at 1200 A UL Type L at <= 600 V","Maximum operating rate":"600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1","inrush power in W (DC)":"390 W","Connections - terminals":"Power circuit: bar 2 - busbar cross section: 52 x 20 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003...0.004 in² (0.2...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004...0.004 in² (0.25...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008...0.002 in² (0.5...1.0 mm²) with cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: solid stranded without cable end Control circuit: push-in 0.001...0.004 in² (0.75...2.5 mm²) - cable stiffness: flexible with cable end","IP degree of protection":"IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106","Rated breaking capacity":"5870 A at 440 V","Pole contact composition":"4 NO","Safety reliability level":"B10d = 100000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 1800000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"7640 A at 440 V","Power dissipation per pole":"70 W AC-1 - Ith 1050 A 42 W AC-3 - Ith 800 A","[Uc] control circuit voltage":"200...500 V AC 50/60 Hz 200...500 V DC","Auxiliary contact composition":"1 NO + 1 NC","[Ui] rated insulation voltage":"1000 V","Control circuit voltage limits":"Operational: 0.8 Uc Min...1.1 Uc Max (at Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))","[Ie] rated operational current":"800 A (at 1050 A (at <104 °F (40 °C)) at <= 1000 V AC-1","[Ue] rated operational voltage":"<= 460 V DC","inrush power in VA (50/60 Hz, AC)":"670 VA","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","hold-in power consumption in W (DC)":"11 W","Ambient Air Temperature for Operation":"-13...140 °F (-25...60 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"5.5 kA - 10 s 4.6 kA - 30 s 3.6 kA - 1 min 2.6 kA - 3 min 1.7 kA - 10 min","[Ith] conventional free air thermal current":"1050 A (at 104 °F (40 °C))","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95daa3bff58913fc774dd1c78237532f.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1G8004LSEN/contactor-high-power-tesys-giga-4p4no-ac1-440v-1050a-standard-version-200500v-ac-dc-wide-band-coil-800a-frame/"},"ai":{"faq":[{"question":"What compliance certifications does this contactor carry?","answer":"It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40:Annex JJ."},{"question":"What is the coil voltage range and type?","answer":"The control circuit voltage is 200...500 V AC 50/60 Hz or 200...500 V DC. The coil includes built-in bidirectional peak limiting."},{"question":"What are the main utilisation categories for this contactor?","answer":"It covers AC-3, AC-3e, AC-1, AC-5a, AC-5b, AC-6a, AC-6b, DC-1, DC-3, and DC-5. For motor loads, AC-3 is the primary rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1G8004LSEN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1G8004LSEN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}