{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K06013M72","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K06013M72","canonicalUrl":"https://aoctrl.com/schneider/LC1K06013M72","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K06013M72","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 6 A, 1 NC auxiliary, 220-230 V AC coil, built-in bidirectional peak limiting diode suppressor.","salesMarkdown":"The TeSys K family is a compact, economy line within the broader TeSys contactor range. For a BOM freeze, the LC1K06013M72 is a stable line item with no imminent replacement. ## Integration notes The 1 NC auxiliary contact is built in; no add-on block required for basic feedback. Short-time withstand current ratings: 90 A for 1 s, 85 A for 5 s, 80 A for 10 s, 60 A for 30 s on the power circuit. These numbers govern coordination with upstream protection — a C-curve MCB or gG fuse sized to the motor FLC will keep the contactor within its let-through capability.","metaTitle":"Schneider TeSys K LC1K06013M72 Contactor, 3P AC-3 6A, 220-23","metaDescription":"Active TeSys K contactor, 3 poles, AC-3 rated 6 A at ≤440 V, 1 NC auxiliary, 220-230 V AC coil with built-in diode suppressor. UL 94 V1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Product name":"TeSys K","Motor power kW":"1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz","Coil technology":"Built-in bidirectional peak limiting diode suppressor","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Device short name":"LC1K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-3 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"6 A at 10 MOhm for signalling circuit","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1K06013M72/tesys-k-contactor-3p-ac3-440-v-6-a-1-nc-aux-220-230-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K06013M72/alternatives.json"},"ai":{"faq":[{"question":"What motor power can this contactor handle?","answer":"It handles 1.5 kW at 220-230 V AC, 2.2 kW at 380-415 V AC, and 3 kW at 440 V through 690 V AC (50/60 Hz). The rating depends on line voltage."},{"question":"Does the coil need an external suppression diode?","answer":"No. The coil has a built-in bidirectional peak limiting diode suppressor. No external snubber or flyback diode is required."},{"question":"What are the physical dimensions?","answer":"Width 45 mm, height 58 mm, depth 57 mm. It is a compact three-pole contactor for DIN-rail mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K06013M72","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K06013M72 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}