{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K06016BLS207","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K06016BLS207","canonicalUrl":"https://aoctrl.com/schneider/LC1K06016BLS207","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K06016BLS207","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K LC1K06016BLS207, 3-pole contactor, AC-3 6A at 440V, 24VDC low-consumption coil with integral suppression, 1NC auxiliary contact, IP20 finger-safe, DIN rail mount.","salesMarkdown":"The Schneider Electric TeSys K LC1K06016BLS207 is a 3-pole contactor rated for AC-3 duty at 6 A at up to 440 V — that is the motor-switching current, not the resistive load. The AC-3 utilisation category means it handles starting and plugging of squirrel-cage motors, where the inrush can be 5–7 times the rated current. The 6 A AC-3 figure governs the motor it can switch; for a typical 400 V three-phase induction motor, this covers about 2.2 kW. The 24 VDC coil is a low-consumption type drawing 1.8 W holding power with integral suppression built in, so no external flyback diode is needed on the control circuit. Coil voltage tolerance is wide: it operates from 0.7 to 1.3 times the rated control voltage (Uc) and drops out reliably at 0.1 Uc below 50 °C. That gives you about 16.8 V to 31.2 V operating range on a nominal 24 VDC supply, with dropout below 2.4 V — useful for brownout ride-through or long cable runs where voltage drop matters. The 1 NC auxiliary contact is instantaneous type, rated for signalling circuits down to 5 mA at 17 V minimum. That low-level switching capability means it works with PLC digital inputs and safety relays without needing a separate interface relay. Mounts on DIN rail or plate via the rail/plate support. The 45 mm width (3 module spaces) and 57 mm depth keep it compact for dense control panels. Power circuit connections use ring lugs with a 7 mm outer diameter, torqued to 0.8–1.3 N·m using a 3.2 mm flat or Phillips No. 2 screwdriver. The operating time — 10–20 ms to open NO contacts on coil de-energisation, 30–40 ms to close on energisation — is relevant for sequencing logic and safety circuit timing. Rated for 3600 cycles per hour maximum operating rate, with mechanical durability of 30 million cycles. Electrical durability is 1.3 million cycles at 6 A AC-3 at up to 440 V — that is the practical life under motor load. Certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1 — so it is accepted across European, North American, Chinese, and Japanese installations. Flame retardance is V0 per UL 94.","metaTitle":"Schneider TeSys K LC1K06016BLS207 Contactor, 6A AC-3, 24VDC","metaDescription":"Schneider Electric TeSys K LC1K06016BLS207 contactor, 3-pole, 6A AC-3 at 440V, 24VDC low-consumption coil with 1NC aux. Active production. UL/CSA/IEC certified. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1","Operating time":"10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing","Coil technology":"With integral suppression device","lifecycle_stage":"current","Flame retardance":"V0 conforming to UL 94","Heat dissipation":"1.8 W","Mounting support":"Rail Plate","Device short name":"LC1K","Inrush power in W":"1.8 W (at 20 °C)","Poles description":"3P","Tightening torque":"Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm flat Ø 6 mm Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm Philips No 2 Power circuit: 0.8...1.3 N.m - on lugs-ring terminals pozidriv No 2","Device application":"Control","Operating altitude":"2000 m without derating","Non overlap distance":"0.5 mm","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-3e AC-4","Contactor application":"Motor control","Electrical durability":"1.3 Mcycles 6 A AC-3 at Ue <= 440 V","Mechanical durability":"30 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NC","Connections - terminals":"Power circuit: lugs-ring terminals (external diameter: 7 mm)","IP degree of protection":"IP20 conforming to VDE 0106","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Signalling circuit frequency":"<= 400 Hz","Control circuit voltage limits":"Operational: 0.7...1.3 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)","Hold-in power consumption in W":"1.8 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5dd31180b2fcde44d2fa98a9eac14ae7.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K06016BLS207/contactor-tesys-k-3p-ac3-440v-6a-1nc-aux-24v-dc-low-consumption-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K06016BLS207/alternatives.json"},"ai":{"faq":[{"question":"What motor size does the 6 A AC-3 rating cover?","answer":"At 400 V three-phase, 6 A AC-3 typically covers a 2.2 kW induction motor. The AC-3 category handles motor starting and plugging, not just resistive loads."},{"question":"Does this contactor need an external coil suppression diode?","answer":"No. The coil has an integral suppression device built in, so no external flyback diode is required on the 24 VDC control circuit."},{"question":"What are the mounting dimensions?","answer":"Width is 45 mm, height 58 mm, depth 57 mm. It mounts on DIN rail or plate via the rail/plate support."},{"question":"What compliance certifications does it carry?","answer":"Certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. Flame retardance is V0 per UL 94."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K06016BLS207","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K06016BLS207 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}