{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K06105G7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K06105G7","canonicalUrl":"https://aoctrl.com/schneider/LC1K06105G7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K06105G7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3P, AC-3 ≤440 V 6 A, 1 NO auxiliary contact, 120 V AC coil.","salesMarkdown":"The Schneider LC1K06105G7 is a TeSys K three-pole contactor rated for AC-3 and AC-4 duty, meaning it switches motor loads — not just resistive heaters. The AC-3 rating of 6 A at ≤440 V covers small three-phase motors up to 1.5 kW at 230 V or 2.2 kW at 400 V, and up to 3 kW on 480 V and higher supplies. The 120 V AC coil pulls in reliably on the control voltage you'd expect from a standard panel transformer. The 6 A rating is the operational current in AC-3 category — the one that governs motor switching. The short-time withstand current (Icw) of 90 A for 1 second means it can ride through a locked-rotor inrush without welding contacts. Heat dissipation is only 1.3 W, so you can pack it tight on a DIN rail without cooking adjacent devices.","metaTitle":"Schneider LC1K06105G7 TeSys K Contactor, 3P, 6A, 120V AC Coi","metaDescription":"Schneider LC1K06105G7 TeSys K contactor, 3P, AC-3 6A, 1 NO aux, 120V AC coil. Obsolete — sourced to order against RFQ. Motor power up to 3 kW.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Product name":"TeSys K","Motor power kW":"1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Device short name":"LC1K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-3 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"6 A at 10 MOhm for signalling circuit","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b3400dc0da5c2e877da5124394ca8e23.pdf","sourceUrl":"https://www.se.com/mk/en/product/LC1K06105G7/tesys-k-contactor-3p-ac3-440-v-6-a-1-no-aux-120-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K06105G7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1K06105G7?","answer":"AC-3 rated operational current 6 A at ≤440 V. Motor power up to 3 kW depending on supply voltage. Coil 120 V AC. Three main poles, one NO auxiliary contact."},{"question":"What is the physical size of the LC1K06105G7?","answer":"45 mm wide, 58 mm high, 57 mm deep — standard 45 mm DIN-rail footprint."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K06105G7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K06105G7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}