{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K06105T7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K06105T7","canonicalUrl":"https://aoctrl.com/schneider/LC1K06105T7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K06105T7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3P, AC-3 <= 440 V 6 A, 1 NO aux., 480 V AC coil, obsolete.","salesMarkdown":"The coil is 480 V AC, so it pulls in on a 480 V control circuit. A single NO auxiliary contact is built in for feedback or interlocking. Motor power capability varies with line voltage: 1.5 kW at 220–230 V, 2.2 kW at 380–415 V, and 3 kW at 440 V through 690 V. Heat dissipation is 1.3 W — negligible in a crowded panel, but worth noting if you are packing relays next to temperature-sensitive electronics.","metaTitle":"Schneider LC1K06105T7 TeSys K Contactor, 6A AC-3, 480V Coil","metaDescription":"Obsolete TeSys K contactor, 3P, AC-3 6A at 440V, 1 NO aux contact, 480V AC coil. Sourced to order against RFQ. Motor power 1.5-3 kW depending on line voltage.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Product name":"TeSys K","Motor power kW":"1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Device short name":"LC1K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-3 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"6 A at 10 MOhm for signalling circuit","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/823a4c5a003ea0c8e7de84fba6d3f6b0.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC1K06105T7/tesys-k-contactor-3p-ac3-440-v-6-a-1-no-aux-480-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K06105T7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Three-pole, normally open. Rated operational current is 6 A in AC-3 utilisation category (motor switching) up to 440 V. Coil is 480 V AC. Motor power ranges from 1.5 kW at 220–230 V up to 3 kW at 440–690 V. One NO auxiliary contact is included."},{"question":"What compliance documentation does Schneider provide for this part?","answer":"The part carries UL 94 V1 flame retardance rating and meets NF F 16-101 and NF F 16-102 Requirement 2 for fire behaviour. Standard Schneider declarations for RoHS and REACH would apply to the original production batch; for surplus stock, compliance documentation depends on the specific lot and should be requested at time of quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K06105T7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K06105T7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}