{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K06106R7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K06106R7","canonicalUrl":"https://aoctrl.com/schneider/LC1K06106R7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K06106R7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, LC1K06106R7, 3-pole, AC-3 6 A at ≤440 V, 1 NO auxiliary contact, 440 V AC 50/60 Hz coil.","salesMarkdown":"The LC1K06106R7 is a 3-pole TeSys K contactor rated 6 A in AC-3 duty at ≤440 V, meaning it switches three-phase motor loads up to that current — the AC-3 category covers starting and stopping squirrel-cage motors under load. Motor power equivalents are 1.5 kW at 220–230 V, 2.2 kW at 380–415 V, and 3 kW at 440–690 V, so the same contactor covers a 400 V class motor in Europe and a 480 V motor in North America without a frame size change. The 440 V AC coil draws its control voltage from the line side or a separate control transformer; verify the coil matches your control circuit voltage before panel wiring. The contactor carries AC-4 ratings as well, which covers plugging and inching duty where the motor is reversed or jogged under load — a harder switching condition that derates the current. For pure AC-4 use, expect to downrate from the 6 A AC-3 figure. The 1 NO auxiliary contact is built in; additional aux blocks can be added on the side for feedback or interlocking.","metaTitle":"Schneider LC1K06106R7 TeSys K Contactor, 3P 6A AC-3, 440V AC","metaDescription":"Active-production TeSys K contactor, 3P, AC-3 6A at ≤440V, 1 NO aux, 440V AC coil. Motor ratings: 1.5 kW at 230V, 2.2 kW at 400V, 3 kW at 480V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","title":"LC1K06106R7","Height":"58 mm","description":"TeSys K contactor, 3P, AC-3 <= 440 V 6 A, 1 NO aux., 440 V AC coil","Product name":"TeSys K","Motor power kW":"1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 480 V AC 50/60 Hz 3 kW at 500...600 V AC 50/60 Hz 3 kW at 660...690 V AC 50/60 Hz","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Device short name":"LC1K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-4 AC-3","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"6 A at 10 MOhm for signalling circuit","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/eba95c4a029ce4afc4da7f5fe356cf6a.pdf","sourceUrl":"https://www.se.com/in/en/product/LC1K06106R7/tesys-k-contactor-3p-ac3-440-v-6-a-1-no-aux-440-v-ac-coil/"},"ai":{"faq":[{"question":"What motor sizes does the LC1K06106R7 cover?","answer":"It covers 1.5 kW at 220–230 V AC, 2.2 kW at 380–415 V AC, and 3 kW at 440–690 V AC, all at 50/60 Hz. This means one contactor handles a 2.2 kW European 400 V motor or a 3 kW North American 480 V motor."},{"question":"What compliance documentation is available for this contactor?","answer":"The contactor carries UL 94 V1 flame retardance and NF F 16-101/102 Requirement 2 for railway fire safety. RoHS and REACH declarations are available from the manufacturer."},{"question":"What is the closest alternative in the TeSys K family?","answer":"The LC1K0610 is the same frame with a 6 A AC-3 rating but a different coil voltage. If your control circuit is 440 V AC, this LC1K06106R7 is the correct coil variant. For a 24 V DC coil or 230 V AC coil, the order code suffix changes — the base contactor body and aux contact count are identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K06106R7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K06106R7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}