{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K0610B5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K0610B5","canonicalUrl":"https://aoctrl.com/schneider/LC1K0610B5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K0610B5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys K contactor, LC1K0610B5, 3-pole, 6 A AC-3/AC-3e, ≤440 V, 1 NO auxiliary contact, 24 V 50 Hz coil.","salesMarkdown":"The Schneider LC1K0610B5 is a TeSys K contactor — a compact 3-pole unit rated for 6 A in AC-3 duty (motor switching) and AC-3e, up to 440 V. It carries a single normally-open auxiliary contact and a 24 V 50 Hz coil without a built-in suppressor module, so you'll need to add a flyback diode or RC snubber externally if the driving circuit demands it. The AC-3 category means it's built for starting and stopping squirrel-cage motors under load — the 6 A rating covers small motors up to roughly 2.2 kW at 400 V. The AC-3e suffix confirms it meets the energy-efficiency test profile for contactors in motor circuits. Screw-clamp terminals accept 1.5 to 4 mm² solid or 0.34 to 2.5 mm² flexible with ferrules; torque range is 0.8 to 1.3 N·m, which is typical for this frame size. Heat dissipation is 1.3 W at coil hold-in, so no special ventilation is needed in a standard enclosure. The 6 A AC-3 rating is the headline number, but the electrical durability tells the real story: 1.3 million cycles at 6 A AC-3, versus only 50,000 cycles at 36 A AC-4 (inching/plugging duty). If your application involves frequent jogging or reversing, the AC-4 life is the limiting factor — plan for replacement sooner. Mechanical durability is 10 million cycles, so the coil and armature will outlast the contacts under heavy AC-4 use. The minimum switching capability is 5 mA at 17 V for signalling circuits — useful if you're switching a PLC input or a low-power relay in the same contactor block. Below that threshold, the oxide film on silver-alloy contacts may not break down reliably. Certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1 — covers the major industrial markets globally. Also listed for IEC 60335-1 and UL 60335-2-40, which matters if the contactor ends up in a heating or refrigeration appliance circuit. Flame retardance is V-1 per UL 94.","metaTitle":"Schneider LC1K0610B5 TeSys K Contactor 6A AC-3 24V 50Hz 3P 1","metaDescription":"Schneider LC1K0610B5 TeSys K contactor, 6A AC-3/AC-3e, 3 poles, 1 NO aux, 24V 50Hz coil. Current lifecycle stage. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"57 mm","Width":"45 mm","Height":"58 mm","IP Rating":"IP20","Application":"Motor control","Operating Time":"10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing","Product Status":"Active","Temp Storage Max":"80 °C","Temp Storage Min":"-50 °C","Temperature Storage":"-50...80 °C","Utilization Category":"AC-3 AC-3e AC-4","Electrical Life Cycles":"1.3 Mcycles 6 A AC-3 at Ue 1.3 Mcycles 6 A AC-3e at Ue 0.05 Mcycles 36 A AC-4 at Ue <= 440 V","Mechanical Life Cycles":"10 Mcycles","Main Product Or Component Type":"Contactor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4e723d6cd4cac426376304c2a4679f03.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K0610B5/contactor-tesys-k-3p-6a-ac3-ac3e-440v-aux-1no-coil-24v-50hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K0610B5/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K0610B5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K0610B5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}