{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K0610P5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K0610P5","canonicalUrl":"https://aoctrl.com/schneider/LC1K0610P5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K0610P5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K LC1K0610P5, 3-pole contactor, 6 A AC-3/AC-3e, 230 V 50 Hz coil, 1 NO auxiliary contact, screw clamp terminals.","salesMarkdown":"## Part identity and motor-duty rating The Schneider Electric LC1K0610P5 is a TeSys K series 3-pole contactor rated for 6 A in AC-3 and AC-3e duty up to 440 V, with a 230 V 50 Hz coil and one normally-open auxiliary contact. The AC-3 category covers starting and stopping of squirrel-cage motors — the 6 A rating corresponds to switching a motor load up to roughly 3 kW at 400 V three-phase. AC-3e is an extended electrical endurance variant of the same duty. Coil hold-in power is 4.5 VA at 20 °C, with inrush of 30 VA. The coil drops out at or above 0.20 Uc below 50 °C, ensuring positive opening on undervoltage. No built-in suppressor module — if your control circuit requires coil surge suppression, add a separate RC snubber or varistor across the coil terminals. ## Electrical endurance and switching life Rated electrical durability is 1.3 million cycles at 6 A AC-3 or AC-3e, and 50,000 cycles at 36 A AC-4 (plugging/inching duty) at voltages up to 440 V. Mechanical endurance is 10 million cycles. The B10d value for safety-related circuits is 1,369,863 cycles under nominal load per EN/ISO 13849-1, or 20 million cycles with mechanical load only — relevant if this contactor is used in a machine safety chain where the auxiliary contact signals contactor state. Maximum operating rate is 3600 cycles per hour. Minimum switching capability for signalling circuits is 5 mA at 17 V — below that, the silver-alloy contacts may not reliably wet, so use a dry-circuit relay for logic-level signals. ## Physical integration and wiring IP20 finger-safe protection per VDE 0106; the terminals are not touch-safe when wired, but the enclosure prevents accidental contact from the front. Screw clamp terminals accept 1.5 to 4 mm² solid or 0.34 to 2.5 mm² flexible with ferrule. Tightening torque is 0.8 to 1.3 N·m (No. 2 Phillips or 6 mm flathead). Heat dissipation is 1.3 W — negligible for thermal budgeting inside a panel, but worth noting if many contactors are ganged in a sealed enclosure.","metaTitle":"LC1K0610P5 TeSys K Contactor, 3P, 6A AC-3, 230V 50Hz Coil","metaDescription":"LC1K0610P5 TeSys K contactor, 3 poles, 6A AC-3/AC-3e, 230V 50Hz coil, 1 NO aux. Active production. Complies with EN/IEC 60947-4-1, UL, CSA. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ","Operating time":"10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Mounting support":"Rail Plate","Device short name":"LC1K","Poles description":"3P","Tightening torque":"0.8...1.3 N.m - on screw clamp terminals Philips No 2 0.8...1.3 N.m - on screw clamp terminals flat Ø 6 mm 0.8...1.3 N.m - on screw clamp terminals pozidriv No 2","Device application":"Control","Inrush power in VA":"30 VA (at 20 °C)","Operating altitude":"2000 m without derating","Non overlap distance":"0.5 mm","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-3e AC-4","Contactor application":"Motor control","Electrical durability":"1.3 Mcycles 6 A AC-3 at Ue 1.3 Mcycles 6 A AC-3e at Ue 0.05 Mcycles 36 A AC-4 at Ue <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NO","Connections - terminals":"Screw clamp terminals 1 cable(s) 1.5...4 mm²solid Screw clamp terminals 1 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34...2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1.5...4 mm²solid Screw clamp terminals 2 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.34...1.5 mm²flexible with cable end","IP degree of protection":"IP20 conforming to VDE 0106","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Signalling circuit frequency":"<= 400 Hz","Control circuit voltage limits":"Operational: 0.8...1.15 Uc (at Drop-out: >= 0.20 Uc (at <50 °C)","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Hold-in power consumption in VA":"4.5 VA (at 20 °C)","Ambient air temperature for storage":"-50...80 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/22ea6744b0ab6d5d3f64a6fac4d9bdd2.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K0610P5/contactor-tesys-k-3p-6a-ac3-ac3e-440v-aux-1no-coil-230v-50hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K0610P5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1K0610P5?","answer":"It is a 3-pole contactor rated 6 A in AC-3/AC-3e duty up to 440 V, with a 230 V 50 Hz coil, one NO auxiliary contact, and screw clamp terminals. Electrical endurance is 1.3 million cycles at AC-3, mechanical endurance 10 million cycles."},{"question":"What compliance documentation is available for the LC1K0610P5?","answer":"The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and GB/T 14048.4. It also meets IEC 60335 appliance standards and has V1 flame retardance per UL 94."},{"question":"What is the mounting and enclosure protection of the LC1K0610P5?","answer":"It mounts on DIN rail or plate, measures 45 x 58 x 57 mm, and has IP20 finger-safe protection per VDE 0106."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K0610P5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K0610P5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}