{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K09013P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K09013P7","canonicalUrl":"https://aoctrl.com/schneider/LC1K09013P7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K09013P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3-pole, AC-3/AC-3e 9A at 440V, 1 NC auxiliary contact, 230V AC coil, spring terminals.","salesMarkdown":"The LC1K09013P7 is a 3-pole contactor from the Schneider TeSys K range, rated 9 A in AC-3 duty at 440 V. That AC-3 category covers squirrel-cage motor starting — switching inductive loads during running, not just resistive make/break. The 9 A figure is the motor current it handles, so it's sized for small motors up to roughly 4 kW at 400 V three-phase. The coil is 230 V AC, 50/60 Hz, with a hold-in draw of 4.5 VA and inrush of 30 VA at 20 °C. No built-in suppressor module, so plan for external RC snubber or varistor if the PLC output driving it needs protection. It carries one normally-closed instantaneous auxiliary contact (1 NC) built in. That's enough for a feedback interlock or a status signal back to the controller. Spring terminals accept one solid or two flexible cables 0.75–1.5 mm², no ferrules needed. Strip length is about 8 mm; the spring cage holds solid and stranded alike without retightening. IP2X finger protection per VDE 0106 means it's safe for open-panel mounting where operators might reach in. No washdown rating — keep it dry or in a sealed enclosure. ## Durability and reliability numbers that matter Mechanical life is 10 million cycles — the contactor itself will outlast most machines. Electrical durability at the AC-3 rating is 1.3 million cycles, which is strong for a compact frame. At AC-4 (plugging/inching) it drops to 20,000 cycles, so don't use it for frequent reversing without derating. Safety reliability B10d is 1,369,863 cycles at nominal load per EN/ISO 13849-1. That's a solid number for a safety-related switching element in a Category 2 or 3 architecture. Heat dissipation is 1.3 W — negligible for panel thermal budgeting. Maximum operating rate is 3600 cycles per hour, so it can keep up with fast indexing or cycling loads.","metaTitle":"Schneider LC1K09013P7 TeSys K Contactor, 3P, 9A AC-3, 230V A","metaDescription":"Schneider Electric TeSys K contactor LC1K09013P7, 3-pole, 9A AC-3/AC-3e at 440V, 1NC aux, 230V AC coil. Active production, global standards. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Standards":"EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ","Operating time":"10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing","Coil technology":"Without built-in suppressor module","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Mounting support":"Plate Rail","Device short name":"LC1K","Poles description":"3P","Device application":"Control","Inrush power in VA":"30 VA (at 20 °C)","Operating altitude":"2000 m without derating","Non overlap distance":"0.5 mm","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-3e AC-1 AC-4","Contactor application":"Resistive load Motor control","Electrical durability":"1.3 Mcycles 9 A AC-3 at Ue 1.3 Mcycles 9 A AC-3e at Ue 0.16 Mcycles 20 A AC-1 at Ue 0.02 Mcycles 54 A AC-4 at Ue <= 440 V","Mechanical durability":"10 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NC","Connections - terminals":"Spring terminals 1 cable(s) 0.75...1.5 mm²solid Spring terminals 1 cable(s) 0.75...1.5 mm²flexible without cable end Spring terminals 2 cable(s) 0.75...1.5 mm²flexible without cable end","IP degree of protection":"IP2X conforming to VDE 0106","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Signalling circuit frequency":"<= 400 Hz","Control circuit voltage limits":"Operational: 0.8...1.15 Uc (at Drop-out: >= 0.20 Uc (at <50 °C)","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Hold-in power consumption in VA":"4.5 VA (at 20 °C)","Ambient air temperature for storage":"-50...80 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b769d82c9ff29dfa7e53646532e0337.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K09013P7/contactor-tesys-k-3p-ac3-ac3e440v-9a-1nc-aux-230v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K09013P7/alternatives.json"},"ai":{"faq":[{"question":"What standards does this contactor comply with?","answer":"It complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and the glow-wire tests in IEC 60335-1 and -2-40."},{"question":"What is the coil voltage and power consumption?","answer":"Coil is 230 V AC, 50/60 Hz. Inrush is 30 VA, hold-in is 4.5 VA at 20 °C. No built-in suppressor."},{"question":"What wire sizes fit the spring terminals?","answer":"Spring terminals accept 1 solid or 2 flexible cables 0.75–1.5 mm² without ferrules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K09013P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K09013P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}