{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K09013Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K09013Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1K09013Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K09013Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3 poles, AC-3 9 A at ≤440 V, 380…400 V AC 50/60 Hz coil, 1 NC auxiliary contact.","salesMarkdown":"The Schneider TeSys K LC1K09013Q7 is a 3-pole contactor rated for motor switching in AC-3 duty at 9 A up to 440 V, with a 380…400 V AC 50/60 Hz coil. It carries one normally-closed auxiliary contact. The AC-3 rating means it handles the inrush of a squirrel-cage induction motor during starting and breaks the running current — the standard utilisation category for motor contactors. Motor power capability spans the voltage range: 2.2 kW at 220…230 V, 4 kW at 380…415 V, 4 kW at 440 V, 4 kW at 480 V, and 4 kW at 500…600 V and 660…690 V, all at 50/60 Hz. This means the contactor delivers the same 4 kW motor rating across most common European and North American industrial voltages above 380 V, simplifying BOM planning when line voltage varies by site. No broker or surplus hunt is needed. The TeSys K family is widely stocked, so lead times are typically short, but as with any active line, a firm RFQ confirms the current allocation.","metaTitle":"Schneider TeSys K LC1K09013Q7 Contactor, 3P, 9A AC-3, 380-40","metaDescription":"Schneider TeSys K LC1K09013Q7 contactor, 3P, AC-3 9A at ≤440V, 380-400V AC 50/60Hz coil, 1 NC aux. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Product name":"TeSys K","Motor power kW":"4 kW at 480 V AC 50/60 Hz 4 kW at 500...600 V AC 50/60 Hz 4 kW at 660...690 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 4 kW at 380...415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Device short name":"LC1K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-3 AC-1 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa12ae823d2dcb8ee17efdeca9722d41.pdf","sourceUrl":"https://www.se.com/in/en/product/LC1K09013Q7/tesys-k-contactor-3p-ac3-440-v-9-a-1-nc-aux-380-400-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K09013Q7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to know for motor switching?","answer":"The contactor is rated 9 A in AC-3 duty at ≤440 V, which translates to 4 kW motor power at 380…415 V, 440 V, 480 V, 500…600 V, and 660…690 V (all at 50/60 Hz). At 220…230 V the motor power rating drops to 2.2 kW. The coil is 380…400 V AC 50/60 Hz."},{"question":"Does the LC1K09013Q7 carry flame-retardance approvals for rail or transit applications?","answer":"Yes. It meets V1 per UL 94 and Requirement 2 per NF F 16-101 and NF F 16-102, making it suitable for rolling-stock and public-transport equipment where fire-smoke-toxicity compliance is required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K09013Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K09013Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}