{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K09103E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K09103E7","canonicalUrl":"https://aoctrl.com/schneider/LC1K09103E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K09103E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K contactor, 3-pole, AC-3 9 A at ≤ 440 V, 48 V AC coil, 1 NO auxiliary contact, depth 57 mm.","salesMarkdown":"The LC1K09103E7 is a Schneider Electric TeSys K contactor, a 3-pole device rated 9 A in AC-3 utilisation category at ≤ 440 V, with a 48 V AC coil and one normally open auxiliary contact. The AC-3 rating means it is sized for switching squirrel-cage motors — the 9 A figure governs the motor full-load current it can handle, not the resistive-heater current. The same contactor also carries AC-1 (resistive) and AC-4 (plugging/inching) ratings, but the AC-3 number is the one that decides fit for most conveyor, pump, and fan loads. Motor power equivalents are listed across common supply voltages: 4 kW at 480 V, 500–600 V, 660–690 V, 380–415 V, and 440 V; 2.2 kW at 220–230 V — all at 50/60 Hz. That covers the bulk of standard three-phase industrial supplies in North America and Europe.","metaTitle":"Schneider TeSys K LC1K09103E7 Contactor, 3P, 9A AC-3, 48V Co","metaDescription":"Obsolete TeSys K contactor, 3P, AC-3 9A at ≤440V, 48V AC coil, 1 NO aux. Sourced to order against RFQ. Depth 57mm. Cite L1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"2.2 in (57 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"2.3 in (58 mm)","Product name":"TeSys K","Motor power kW":"4 kW 480 V AC 50/60 Hz 4 kW 500...600 V AC 50/60 Hz 4 kW 660...690 V AC 50/60 Hz 2.2 kW 220...230 V AC 50/60 Hz 4 kW 380...415 V AC 50/60 Hz 4 kW 440 V AC 50/60 Hz","lifecycle_stage":"current","Flame retardance":"V1 UL 94 Requirement 2 NF F 16-101 Requirement 2 NF F 16-102","Heat dissipation":"1.3 W","Range of product":"TeSys K","Poles description":"3P","Compatibility code":"LC1K","Device application":"Control","Utilisation category":"AC-3 AC-1 AC-4","Pole contact composition":"3 NO","Product or component type":"Contactor","[Ie] rated operational current":"20 A (at 9 A at 16 A (at 10 MOhm for signalling circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6b254eba8fad6533a71e3441b7b99f80.pdf","sourceUrl":"https://www.se.com/in/en/product/LC1K09103E7/tesys-k-contactor-3p-ac3-440-v-9-a-1-no-aux-48-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K09103E7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LC1K09103E7?","answer":"It is a 3-pole contactor rated 9 A in AC-3 (motor switching) at ≤ 440 V, with a 48 V AC coil and one NO auxiliary contact. Motor power equivalents range from 2.2 kW at 220–230 V up to 4 kW at 480–690 V, 50/60 Hz."},{"question":"What are the physical dimensions of the LC1K09103E7?","answer":"Width 45 mm, height 58 mm, depth 57 mm. It mounts on a 35 mm DIN rail."},{"question":"What compliance documentation is available for this part?","answer":"The moulded case is rated V-1 per UL 94 and meets NF F 16-101 and NF F 16-102 flame-retardance standards. The part belongs to the TeSys K range, which typically carries UL, CSA, and CE markings, though specific certificates for this exact obsolete code should be confirmed from archived documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K09103E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K09103E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}