{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K0986BLS207","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K0986BLS207","canonicalUrl":"https://aoctrl.com/schneider/LC1K0986BLS207","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K0986BLS207","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LC1K contactor, LC1K0986BLS207, 4-pole, 24 V DC coil with integral suppression, 20 A AC-1 rated operational current, IP20.","salesMarkdown":"It's rated for 20 A in AC-1 utilisation category (resistive loads) at up to 690 V, so it's sized for switching heater banks, lighting, or other non-inductive loads in a control panel. The contact arrangement is 2 NO + 2 NC, giving you flexibility for both power and auxiliary signalling on the same device. The coil holds in at 0.7 to 1.3 times Uc (16.8 to 31.2 V DC) and drops out below 0.1 Uc (2.4 V DC), so it's tolerant of a sagging 24 V supply but will drop cleanly on a brownout. The 1.8 W hold-in power at 20 °C means it won't cook neighbouring components in a tightly packed enclosure. The power circuit connections use ring terminals with an external diameter of 7 mm, torqued to 0.8–1.3 N·m.","metaTitle":"Schneider TeSys LC1K0986BLS207 Contactor, 24 V DC, 20 A AC-1","metaDescription":"Schneider TeSys LC1K0986BLS207 contactor, 24 V DC coil, 20 A AC-1 at ≤690 V, 4 poles (2 NO + 2 NC), IP20, current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","title":"LC1K0986BLS207","Height":"58 mm","Standards":"BS 5424 IEC 60947 NF C 63-110 VDE 0660 IEC 60077-1 IEC 60077-2 EN 45545: R22 HL3 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","description":"Contactor, TeSys K, 4P(2NO+2NC), AC-1, 20A, 24V DC low consumption coil","Operating time":"10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing 25...35 ms coil energisation and NC opening 15...25 ms coil de-energisation and NC closing","Coil technology":"With integral suppression device","lifecycle_stage":"current","Flame retardance":"V0 conforming to UL 94","Heat dissipation":"1.8 W","Mounting support":"Plate Rail","Average impedance":"3 mOhm - Ith 20 A 50 Hz for power circuit","Device short name":"LC1K","Inrush power in W":"1.8 W (at 20 °C)","Poles description":"4P","Tightening torque":"Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm flat Ø 6 mm Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm Philips No 2 Power circuit: 0.8...1.3 N.m - on lugs-ring terminals pozidriv No 2","Device application":"Control","Operating altitude":"2000 m without derating","Control circuit type":"DC low consumption","Overvoltage category":"III","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"0.18 Mcycles 20 A AC-1 at Ue <= 440 V","Mechanical durability":"30 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Associated fuse rating":"25 A gG at 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660","Maximum operating rate":"3600 cyc/h","Connections - terminals":"Power circuit: lugs-ring terminals (external diameter: 7 mm)","IP degree of protection":"IP20 conforming to VDE 0106","Rated breaking capacity":"110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"110 A AC for power circuit conforming to IEC 60947","[Uc] control circuit voltage":"24 V DC","[Ui] rated insulation voltage":"Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-5-1 Power circuit: 750 V conforming to VDE 0110 group C Power circuit: 690 V conforming to BS 5424 Power circuit: 690 V conforming to NF C 20-040","Control circuit voltage limits":"Operational: 0.7...1.3 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)","Hold-in power consumption in W":"1.8 W at 20 °C","Power Pole Contact Composition":"2 NO + 2 NC","[Ie] rated operational current":"20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: Signalling circuit: <= 690 V AC <= 400 Hz","Ambient air temperature for storage":"-50...80 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit","[Ith] conventional free air thermal current":"20 A (at 60 °C) for power circuit 10 A (at 50 °C) for signalling circuit","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$92.45","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5f77193a997c4857776090730cc98ad3.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K0986BLS207/contactor-tesys-k-4p2no+2nc-ac1-20a-24v-dc-low-consumption-coil/"},"ai":{"faq":[{"question":"What is the closest alternative to LC1K0986BLS207 in the TeSys family?","answer":"Within the TeSys LC1K range, a direct peer would be a 4-pole contactor with the same coil voltage and pole configuration. The key difference to check is the rated operational current — the LC1K0986BLS207 is specified at 20 A AC-1. If your load requires a different current, look for a sibling with a matching Ie rating and the same 24 V DC coil."},{"question":"What compliance documentation does Schneider provide for this contactor?","answer":"The contactor is certified to IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN 45545 (R22 HL3), and meets V-0 flame retardance per UL 94. Schneider typically provides a Declaration of Conformity covering these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K0986BLS207","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K0986BLS207 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}