{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1K12016FLS207","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1K12016FLS207","canonicalUrl":"https://aoctrl.com/schneider/LC1K12016FLS207","factsUrl":"https://aoctrl.com/api/mcp/products/LC1K12016FLS207","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys LC1K contactor, 3-pole, 12 A AC-3, 24 V DC coil with integral suppression, IP20, 45 x 58 x 57 mm.","salesMarkdown":"It carries a 24 V DC coil with integral suppression, meaning the flyback diode is built in — no external snubber needed on the coil drive. Rated for utilisation categories AC-1, AC-3, AC-3e, and AC-4, the 12 A AC-3 rating at ≤ 440 V is the one that governs motor switching duty — that is the current it can make and break across a typical induction motor load. For resistive loads (AC-1), electrical durability is 0.3 Mcycles at 20 A. This contactor carries approvals across IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN 45545 (R22 HL3) for rail vehicle fire safety. Safety reliability is quantified: B10d = 1,369,863 cycles at nominal load per EN/ISO 13849-1, and 20,000,000 cycles with mechanical load only — useful data for safety circuit design where the contactor is part of the stopping chain. Flame retardance is V0 per UL 94. The spread is clean — no broker hunt required, no last-time-buy window to watch. If your BOM calls this order code, it ships from the regular supply channel. Mounts on rail or plate. Power circuit connections use ring lugs (7 mm outer diameter) with a tightening torque of 0.8 to 1.3 N·m. The auxiliary contact is a single NC instantaneous type. Coil operating time: 10 to 20 ms for de-energisation and NO opening, 30 to 40 ms for energisation and NO closing. Minimum switching capability is 5 mA at 17 V for signalling circuits — important when the auxiliary contact drives a PLC input with low wetting current. Heat dissipation is 1.8 W at 20 °C, both inrush and hold-in.","metaTitle":"Schneider LC1K12016FLS207 TeSys Contactor, 3P, AC-3 12A, 24V","metaDescription":"Schneider Electric TeSys LC1K12016FLS207 contactor, 3-pole, 12 A AC-3, 24 V DC coil with suppression. UL/CSA/IEC certified. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"45 mm","Height":"58 mm","Standards":"BS 5424 IEC 60947 NF C 63-110 VDE 0660 IEC 60077-1 IEC 60077-2 EN 45545: R22 HL3 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Operating time":"10...20 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing","Product weight":"0.235 kg","Coil technology":"With integral suppression device","lifecycle_stage":"current","Flame retardance":"V0 conforming to UL 94","Heat dissipation":"1.8 W","Mounting support":"Rail Plate","Device short name":"LC1K","Inrush power in W":"1.8 W (at 20 °C)","Poles description":"3P","Tightening torque":"Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm flat Ø 6 mm Power circuit: 0.8...1.3 N.m - on lugs-ring terminals - with screwdriver 3.2 mm Philips No 2 Power circuit: 0.8...1.3 N.m - on lugs-ring terminals pozidriv No 2","Device application":"Control","Operating altitude":"2000 m without derating","Non overlap distance":"0.5 mm","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-3e AC-1 AC-4","Contactor application":"Motor control Resistive load","Electrical durability":"0.3 Mcycles 20 A AC-1 at Ue 1.3 Mcycles 12 A AC-3 at Ue <= 440 V","Mechanical durability":"30 Mcycles","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","Maximum operating rate":"3600 cyc/h","Auxiliary contacts type":"type instantaneous 1 NC","Connections - terminals":"Power circuit: lugs-ring terminals (external diameter: 7 mm)","IP degree of protection":"IP20 conforming to VDE 0106","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Minimum switching current":"5 mA for signalling circuit","Minimum switching voltage":"17 V for signalling circuit","Product or component type":"Contactor","Signalling circuit frequency":"<= 400 Hz","Control circuit voltage limits":"Operational: 0.7...1.3 Uc (at Drop-out: >= 0.10 Uc (at <50 °C)","Hold-in power consumption in W":"1.8 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Permissible ambient air temperature around the device":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/da671b9b6564720f1aeff046c36876f8.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1K12016FLS207/contactor-tesys-k-3p-ac3-440v-12a-1nc-aux-110v-dc-low-consumption-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1K12016FLS207/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this contactor carry?","answer":"It is certified to IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN 45545 R22 HL3, and BS 5424. Flame retardance is V0 per UL 94."},{"question":"What is the closest alternative in the TeSys K family?","answer":"The LC1K12016FLS207 is the standard 3-pole, 12 A AC-3, 24 V DC coil variant with integral suppression. A sibling with a different coil voltage (e.g., 110 V AC or 48 V DC) is the same mechanical platform but changes the coil drive requirements — not pin-compatible if your control voltage is fixed at 24 V DC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1K12016FLS207","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1K12016FLS207 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}