{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1SF1200KUE","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1SF1200KUE","canonicalUrl":"https://aoctrl.com/schneider/LC1SF1200KUE","factsUrl":"https://aoctrl.com/api/mcp/products/LC1SF1200KUE","rawCanonicalId":null},"summary":{"shortDescription":"Contactor, TeSys F, 3P(3NO), AC-1 <=440V 1200A, coil 100...250V AC / 100...380V DC","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"232 mm","Range":"TeSys","Width":"233 mm","Height":"338 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1","Operating time":"40...80 ms closing 10...40 ms opening","lifecycle_stage":"unknown","Heat dissipation":"2.2...5.5 W","Mounting support":"Plate","Range of product":"TeSys F","Average impedance":"0.1 mOhm - Ith 1200 A 50 Hz","Device short name":"LC1SF","Inrush power in W":"410...500 W (at 20 °C)","Poles description":"3P","Tightening torque":"Power circuit: 58 N.m Control circuit: 0.6 N.m","Compatibility code":"LC1F","Inrush power in VA":"360...550 VA, 50/60 Hz cos phi 0.5 (at 20 °C)","Operating altitude":"3000 m without derating","Input compatibility":"PLC 24 V DC conforming to IEC 61131-2 Type 2","Control circuit type":"AC at 50/60 Hz electronic DC electronic","Input voltage limits":"0...5 V off-state for PLC input 11...30 V on-state for PLC input","Overvoltage category":"III","Protective treatment":"TH","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical durability":"50000 cycles","Associated fuse rating":"1400 A gG at <= 440 V","Maximum operating rate":"1200 cyc/h 55 °C","Connections - terminals":"Power circuit: bar 2 cable(s) - busbar cross section: 50 x 8 mm Control circuit: screw clamp terminals 1 cable(s) 0.2...2.5 mm²solid Control circuit: screw clamp terminals 1 cable(s) 0.2...2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 0.25...2.5 mm²flexible with cable end","Rated breaking capacity":"1800 A conforming to IEC 60947-4-1","Product or component type":"Contactor","Irms rated making capacity":"1800 A conforming to IEC 60947-4-1","Power dissipation per pole":"120 W AC-1","[Uc] control circuit voltage":"100...250 V AC 50/60 Hz 100...380 V DC","[Ui] rated insulation voltage":"1000 V conforming to IEC 60947-4-1","Control circuit voltage limits":"Operational: 85...275 V AC 50/60 Hz (at 55 °C) Operational: 85...418 V DC (at 55 °C) Drop-out: 0...58 V AC 50/60 Hz (at 55 °C) Drop-out: 0...45 V DC (at 55 °C)","Hold-in power consumption in W":"2.7...5 W at 20 °C","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"1200 A (at 1110 A (at 1020 A (at <70 °C) at <= 440 V AC-1","[Ue] rated operational voltage":"<= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"5...8 VA, 50/60 Hz cos phi 0.5 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"8000 A 40 °C - 10 s 5200 A 40 °C - 30 s 4000 A 40 °C - 1 min 3000 A 40 °C - 3 min 2000 A 40 °C - 10 min","[Ith] conventional free air thermal current":"1200 A (at 40 °C)","Permissible ambient air temperature around the device":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$10,816.25","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e0782c890bfaab846a1086378f19ce06.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1SF1200KUE/contactor-tesys-f-3p3no-ac1-440v-1200a-coil-100-250v-ac-100-380v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1SF1200KUE/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1SF1200KUE","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1SF1200KUE when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}