{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2D80004FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2D80004FE7","canonicalUrl":"https://aoctrl.com/schneider/LC2D80004FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2D80004FE7","rawCanonicalId":null},"summary":{"shortDescription":"Changeover contactor, TeSys Deca, 4P(4 NO), AC-1, <= 440 V 125 A - 115 V AC coil","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"158 mm","Range":"TeSys","Width":"207 mm","Height":"127 mm","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508","Front cover":"Without","Product name":"TeSys Deca","Operating time":"20...35 ms closing 6...20 ms opening","Coil technology":"Without built-in suppressor module","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"mature","Flame retardance":"V1 conforming to UL 94","Heat dissipation":"6...10 W at 50/60 Hz","Mounting support":"Rail Plate","Pollution degree":"3","Average impedance":"0.8 mOhm - Ith 125 A 50 Hz for power circuit","Device short name":"LC2D","Interlocking type":"Mechanical","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm Power circuit: 12 N.m - on connector hexagonal screw head 4 mm","Climatic withstand":"conforming to IACS E10","Inrush power in VA":"245 VA 60 Hz cos phi 0.75 (at 20 °C) 245 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"0...3000 m","Device presentation":"Preassembled, with prewired power connections","Control circuit type":"AC at 50/60 Hz","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-1 AC-3 AC-3e AC-4","Contactor application":"Resistive load","Electrical durability":"0.8 Mcycles 125 A AC-1 at Ue <= 440 V","Mechanical durability":"4 Mcycles","Mechanical robustness":"Vibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor open: 8 Gn for 11 ms Vibrations contactor closed: 3 Gn, 5...300 Hz Shocks contactor closed: 10 Gn for 11 ms","Associated fuse rating":"200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid Control circuit: screw clamp terminals 1 cable(s) 1...2.5 mm²flexible with cable end Power circuit: connector 1 cable(s) 4...50 mm²flexible without cable end Power circuit: connector 2 cable(s) 4...25 mm²flexible without cable end Power circuit: connector 1 cable(s) 4...50 mm²flexible with cable end Power circuit: connector 2 cable(s) 4...16 mm²flexible with cable end Power circuit: connector 1 cable(s) 4...50 mm²solid Power circuit: connector 2 cable(s) 4...25 mm²solid","IP degree of protection":"IP20 front face conforming to IEC 60529","Rated breaking capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Changeover contactor","Irms rated making capacity":"1100 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"12.5 W AC-1","[Uc] control circuit voltage":"115 V AC 50/60 Hz","[Ui] rated insulation voltage":"Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-40...70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...55 °C):operational AC 50 Hz 0.85...1.1 Uc (-40...55 °C):operational AC 60 Hz 1...1.1 Uc (55...70 °C):operational AC 50/60 Hz","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"125 A (at 80 A (at 80 A (at 55 A (at <60 °C) at <= 400 V AC AC-4 for power circuit","[Ue] rated operational voltage":"Power circuit: Power circuit: <= 300 V DC","Hold-in power consumption in VA":"26 VA 60 Hz cos phi 0.3 (at 20 °C) 26 VA 50 Hz cos phi 0.3 (at 20 °C)","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C 60...70 °C with derating","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"135 A 40 °C - 10 min for power circuit 320 A 40 °C - 1 min for power circuit 640 A 40 °C - 10 s for power circuit 990 A 40 °C - 1 s for power circuit","[Ith] conventional free air thermal current":"125 A (at 60 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a2fb23aad9ef296a217bae3428b0205b.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2D80004FE7/changeover-contactor-tesys-deca-4p4-no-ac1-440-v-125-a-115-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2D80004FE7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2D80004FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2D80004FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}