{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K06013F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K06013F7","canonicalUrl":"https://aoctrl.com/schneider/LC2K06013F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K06013F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 6 A, 1 NC, 110 V AC coil, IP20.","salesMarkdown":"It's a 3-pole (3 NO main poles) contactor rated AC-3 at 6 A up to 440 V and AC-4 duty, with a 110 V AC coil and one NC auxiliary contact. The IP20 finger-safe enclosure (per VDE 0106) means it's suited for enclosed panel mounting where accidental contact is prevented. The AC-3 rating of 6 A at <=440 V is the motor-switching current — it handles starting currents of small three-phase motors up to roughly 2.2 kW at 400 V. The 110 V AC coil is a common control voltage in older European panels; verify your control transformer matches before wiring. The NC auxiliary contact provides a feedback signal for the reversing interlock or status indication. Mechanical robustness specs show the contactor holds closed through 10 Gn shocks on Y and Z axes (15 Gn on X when closed) and 4 Gn vibration at 5–300 Hz — this is a rugged unit for industrial environments with moderate vibration, like conveyor lines or pump skids. Operating temperature range is -25 to 50 °C, storage from -50 to 80 °C, and altitude rating is 2000 m without derating. Flame retardance meets V1 per UL 94 and NF F 16-101/102, important for rail and transport applications. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance. At 57 mm deep, 90 mm wide, and 58 mm tall, this reversing contactor fits a compact footprint — about the size of two standard contactors side by side but pre-busbarred. The IP20 rating means it's intended for enclosure mounting where the front panel or door provides the next level of protection. Mounting is via the standard DIN rail clip or screw fixing; the preassembled power busbar reduces wiring errors on reversing applications like motor direction control.","metaTitle":"Schneider TeSys K LC2K06013F7 reversing contactor, 6A AC-3,","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 <=440V 6A, 1 NC, 110V AC coil. Sourced to order against RFQ. Depth 57 mm, width 90 mm, height 58 mm. IP20.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC2K06013F7/tesys-k-reversing-contactor-3p-ac3-440-v-6-a-1-nc-110-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K06013F7/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings for this contactor?","answer":"It is rated AC-3 at 6 A up to 440 V for motor switching, and AC-4 for inching/plugging. The coil is 110 V AC. It has 3 NO main poles and 1 NC auxiliary contact."},{"question":"What physical size is this reversing contactor?","answer":"Depth is 57 mm, width 90 mm, height 58 mm. It has IP20 finger-safe protection."},{"question":"What series and range does this belong to?","answer":"It is part of the Schneider TeSys K range, a compact reversing contactor series for motor control applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K06013F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K06013F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}