{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K06017FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K06017FE7","canonicalUrl":"https://aoctrl.com/schneider/LC2K06017FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K06017FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 6 A, 1 NC, 115 V AC coil, IP20.","salesMarkdown":"The LC2K06017FE7 is a TeSys K reversing contactor from Schneider Electric — a 3-pole unit preassembled with a reversing power busbar, designed for motor control in the AC-3 and AC-4 utilisation categories. It switches motor loads up to 6 A at ≤440 V AC on the AC-3 curve, which covers starting and stopping of squirrel-cage motors under normal running conditions. The AC-4 rating covers plugging and inching duty. The 115 V AC coil is the control side; the 1 NC auxiliary contact provides a feedback or interlock path. At 57 mm deep, 90 mm wide, and 58 mm tall, this reversing contactor occupies a compact footprint on a DIN rail or panel plate. The IP20 degree of protection means it is touch-safe but not sealed against moisture — suitable for enclosed control panels, not washdown environments. The operating temperature range of -25 to 50 °C covers most indoor industrial conditions, with storage tolerance from -50 to 80 °C. The V1 flame retardance rating per UL 94 and NF F 16-101/102 is relevant for rail and transit applications where fire-smoke-toxicity compliance is required.","metaTitle":"Schneider Electric LC2K06017FE7 TeSys K Reversing Contactor,","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 <=440V 6A, 1 NC, 115V AC coil. IP20. Sourced to order against RFQ. Official lifecycle status: Obsolete.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9903c683b138c2622edd4b090bb8ce29.pdf","sourceUrl":"https://www.se.com/mk/en/product/LC2K06017FE7/tesys-k-reversing-contactor-3p-ac3-440-v-6-a-1-nc-115-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K06017FE7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC2K06017FE7 in the TeSys family?","answer":"No official successor order code is listed in the lifecycle record. A form-fit-function replacement would need to match the 3P reversing contactor form factor, AC-3 6 A at ≤440 V rating, 115 V AC coil, and 1 NC auxiliary contact. A parametric search within the current TeSys range (e.g., TeSys Deca or TeSys Giga series) would be the next step, but no direct pin-compatible drop-in is documented here."},{"question":"What is the depth of this contactor?","answer":"The listed depth is 57 mm."},{"question":"What series does LC2K06017FE7 belong to?","answer":"It is part of the TeSys K range, specifically the TeSys K series of contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K06017FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K06017FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}