{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K06103FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K06103FE7","canonicalUrl":"https://aoctrl.com/schneider/LC2K06103FE7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K06103FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3 poles, AC-3 <=440 V 6 A, 1 N/O auxiliary, 115 V AC coil, preassembled with reversing power busbar, IP20 finger-safe.","salesMarkdown":"It's a 3-pole (3 NO main poles) contactor pair in one package, rated for AC-3 duty at 6 A up to 440 V and AC-4 duty, meaning it's sized for small reversing motor loads like conveyors, hoists, or valve actuators where direction change is part of the cycle. The 115 V AC coil is standard for North American control circuits. ## Integration notes — panel fit and wiring The preassembled reversing busbar saves wiring time but locks the contactor pair into a fixed mechanical interlock; there's no field adjustment for contactor spacing. The 115 V AC coil draws its rated inrush and hold current from the control transformer; verify the transformer VA rating can handle the inrush of two contactor coils energising simultaneously during a reversing transition. ## Mechanical and environmental robustness Rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: the contactor holds closed under 10 Gn on Y and Z axes, 4 Gn vibration closed. That's sufficient for most industrial machinery but not for extreme mobile or marine applications where higher shock profiles apply. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is standard for rail and building infrastructure compliance.","metaTitle":"Schneider LC2K06103FE7 TeSys K Reversing Contactor, 6A AC-3,","metaDescription":"Obsolete Schneider TeSys K reversing contactor LC2K06103FE7, 3P, AC-3 6A at 440V, 115V AC coil, IP20. Sourced to order against RFQ via independent channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3becefc010f7c31104712188b51cee65.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2K06103FE7/tesys-k-reversing-contactor-3p-ac3-440-v-6-a-1-no-115-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K06103FE7/alternatives.json"},"ai":{"faq":[{"question":"What replaces the LC2K06103FE7?","answer":"There is no official direct successor listed in the lifecycle record. The TeSys K series has been superseded by the TeSys D range, but a drop-in substitution requires a full panel review because the physical footprint, busbar arrangement, and coil voltage differ. Do not assume a simple MPN swap without verifying fit and ratings."},{"question":"What are the key ratings for the LC2K06103FE7?","answer":"It is a 3-pole reversing contactor rated AC-3 at 6 A up to 440 V and AC-4, with a 115 V AC coil. It has 1 N/O auxiliary contact, IP20 finger-safe protection, and measures 90 x 58 x 57 mm. Operating temperature range is -25 to 50 °C."},{"question":"How do I source the LC2K06103FE7?","answer":"Since it is obsolete, sourcing goes through independent distributor and broker networks. Submit an RFQ with your quantity and target lead time; we will quote against confirmed available inventory. No shelf stock is held for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K06103FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K06103FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}