{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K09013M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K09013M7","canonicalUrl":"https://aoctrl.com/schneider/LC2K09013M7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K09013M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LC2K09013M7, 3P, AC-3 9 A at 440 V, 220-230 VAC 50/60 Hz coil, 1 NC auxiliary contact, preassembled with reversing power busbar.","salesMarkdown":"## What this TeSys K reversing contactor is The LC2K09013M7 is a TeSys K reversing contactor from Schneider Electric — a 3-pole, 3 NO power pole unit rated for motor control in AC-3 duty up to 9 A at 440 V, and for resistive loads in AC-1. The coil is 220-230 VAC 50/60 Hz, and there's one NC auxiliary contact built in. The AC-3 rating of 9 A at 440 V tells you this contactor handles the inrush and break current of a standard squirrel-cage motor up to that current — think small conveyors, pumps, or fans. AC-1 covers resistive loads like heaters at the same current. The 220-230 VAC coil is common across European and many Asian control voltages; just watch that your control transformer is sized for the inrush. IP20 (VDE 0106) means finger-safe terminals but no protection against moisture — it's for inside a clean, dry enclosure.","metaTitle":"Schneider Electric LC2K09013M7 TeSys K Reversing Contactor,","metaDescription":"Schneider Electric LC2K09013M7 TeSys K reversing contactor, 3P, AC-3 9 A at 440 V, 220-230 VAC coil, 1 NC auxiliary. Active production, IP20, UL 94 V1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LC2K09013M7","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 9 A, 1 NC, 220...230 VAC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3 AC-1","Contactor application":"Resistive load Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8ccbe1a033b0be68bcb177b5e6583658.pdf","sourceUrl":"https://www.se.com/in/en/product/LC2K09013M7/tesys-k-reversing-contactor-3p-ac3-440-v-9-a-1-nc-220-230-vac-coil/"},"ai":{"faq":[{"question":"What is the closest alternative to LC2K09013M7 in the TeSys K family?","answer":"The LC2K09013M7 is a reversing contactor preassembled with a reversing busbar. The closest non-reversing sibling is the LC1K0901M7, which is a single contactor (not reversing) with the same 9 A AC-3 rating and 220-230 VAC coil. The reversing assembly saves you the interlock wiring — if you only need forward control, the LC1K saves panel space and cost."},{"question":"What is LC2K09013M7's depth?","answer":"57 mm. Overall dimensions are 57 mm deep, 90 mm wide, and 58 mm high — fits a standard 90 mm wide DIN-rail footprint."},{"question":"What compliance documentation does this contactor carry?","answer":"Flame retardance is V1 per UL 94, and it also meets NF F 16-101 and NF F 16-102 (French rail standards). Protective treatment conforms to IEC 60068 and DIN 50016. The IP20 rating is per VDE 0106. No RoHS or REACH statement is on this record, but standard Schneider TeSys K parts are generally RoHS compliant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K09013M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K09013M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}