{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K12015Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K12015Q7","canonicalUrl":"https://aoctrl.com/schneider/LC2K12015Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K12015Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LC2K12015Q7, 3P, AC-3 12 A at ≤440 V, 380…400 V AC coil, IP20.","salesMarkdown":"The 380…400 V AC coil pulls in across that voltage band, and the contactor is rated for AC-3 duty at 12 A up to 440 V, meaning it switches three-phase squirrel-cage motors on and off under load within that current envelope. It also carries AC-4 ratings for plugging and inching, and AC-1 for resistive loads. The AC-3 12 A rating at ≤440 V is the headline motor-switching figure — it governs the maximum full-load current of the motor you can reverse with this contactor. For a 400 V three-phase induction motor, 12 A AC-3 corresponds roughly to a 5.5 kW output, though you should verify locked-rotor current and duty cycle against the AC-4 curve if the application involves frequent reversing under load. The coil is wound for 380…400 V AC 50/60 Hz, so it drops straight into a European 400 V line without a control transformer. Flame retardance meets V1 per UL 94 and NF F 16-101/102, which is relevant for rail and transport applications. The preassembled reversing busbar saves installation time compared to building a reversing pair from two individual contactors plus a mechanical interlock. ## Mechanical robustness for industrial environments The contactor is rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6. With the contactor closed, it withstands 10 Gn on X axis and 15 Gn on Y and Z axes for 11 ms; open, it handles 6 Gn on X and 10 Gn on Y and Z. Vibration resistance is 4 Gn closed and 2 Gn open across 5…300 Hz. These figures matter for applications mounted on machinery or in mobile equipment where mechanical shock is a risk.","metaTitle":"TeSys K LC2K12015Q7 Reversing Contactor, 3P, AC-3 12A, 380-4","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 12A at 440V, 380-400V AC coil. IP20. Sourced to order against RFQ via surplus channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"57 mm","Width":"90 mm","Height":"58 mm","IP Rating":"IP20","Application":"Resistive load Motor control","Product Status":"Active","Temp Storage Max":"80 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...80 °C","Utilization Category":"AC-3 AC-4 AC-1","Main Product Or Component Type":"Reversing contactor","Ambient Air Temperature Operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d55c34c2745426cfecb0a1d0741c55ce.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC2K12015Q7/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-nc-380-400-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K12015Q7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K12015Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K12015Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}