{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K1210U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K1210U7","canonicalUrl":"https://aoctrl.com/schneider/LC2K1210U7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K1210U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LC2K1210U7, 3P, AC-3 12A at 440V, 230-240VAC coil, preassembled with reversing busbar.","salesMarkdown":"AC-3 at 12 A is the motor-switching rating — it's what governs the contactor's ability to make and break locked-rotor current. That 12 A at 440 V covers a 5.5 kW (7.5 HP) motor at 400 V three-phase. The AC-4 rating covers plugging and inching duty, which is lower; if you're reversing under load frequently, derate accordingly. The preassembled reversing busbar saves panel-build time — the mechanical interlock and power bus are already integrated, so you wire the line and load sides directly. The 57 mm depth and 90 mm width mean it fits standard 45 mm DIN-rail spacing with room for adjacent devices. Operating altitude is 2000 m without derating. Above that, you'll need to account for reduced air density on the arc extinction and thermal dissipation.","metaTitle":"Schneider TeSys K LC2K1210U7 Reversing Contactor, 3P, AC-3 1","metaDescription":"Schneider Electric TeSys K reversing contactor LC2K1210U7. 3P, AC-3 12A at 440V, 230-240VAC coil. Obsolete — sourced to order against RFQ. IP20 finger-safe.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"57 mm","Width":"90 mm","Height":"58 mm","IP Rating":"IP20","Application":"Resistive load, Motor control","Product Status":"Active","Temp Storage Max":"80 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...80 °C","Utilization Category":"AC-3 AC-4 AC-1","Main Product Or Component Type":"Reversing contactor","Ambient Air Temperature Operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fa1992abd22804eba0483bd6f9005608.pdf","sourceUrl":"https://www.se.com/ca/en/product/LC2K1210U7/tesys-k-reversing-contactor-3p-ac3-440-v-12-a-1-no-230-240-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K1210U7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K1210U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K1210U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}