{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K1601F72","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K1601F72","canonicalUrl":"https://aoctrl.com/schneider/LC2K1601F72","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K1601F72","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 16 A, 1 NC auxiliary, 110 V AC coil, IP20, preassembled with reversing power busbar.","salesMarkdown":"The Schneider Electric TeSys K LC2K1601F72 is a reversing contactor — three poles, normally open, with one normally closed auxiliary contact built in. The reversing pair is preassembled with the power busbar, so it lands as one unit ready for the panel. AC-3 rating is the one that matters for motor starting: 16 A at 440 V means it handles a 7.5 kW induction motor on a 400 V line without derating. The AC-4 category also covers plugging and inching duty, so it's not limited to simple start/stop. IP20 finger-safe terminals per VDE 0106 mean it's suited for enclosed control panels where accidental contact is a concern. The preassembled reversing busbar saves wiring time — no need to build the interlock loop externally. Operating altitude is 2000 m without derating, so it works at most plant elevations. That covers unheated warehouses and warm cabinet interiors. The 110 V AC coil is a common control voltage in North American and some European panels. If your plant standardizes on 24 V DC or 230 V AC, you'd look at the coil variant in the same TeSys K family — same contactor body, different coil code.","metaTitle":"Schneider TeSys K LC2K1601F72 Reversing Contactor, 16 A, 110","metaDescription":"Schneider TeSys K LC2K1601F72 reversing contactor, 3P, AC-3 <=440 V 16 A, 1 NC, 110 V AC coil. IP20, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LC2K1601F72","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NC, 110 V AC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a950c74744913877cda525f7c427d775.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2K1601F72/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-nc-110-v-ac-coil/"},"ai":{"faq":[{"question":"What are the key ratings for this reversing contactor?","answer":"It's a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 110 V AC coil. The power circuit handles 690 V AC 50/60 Hz. It has one NC auxiliary contact and is preassembled with the reversing power busbar."},{"question":"What compliance documentation does Schneider provide for LC2K1601F72?","answer":"The contactor carries IP20 protection per VDE 0106, flame retardance V1 per UL 94, and meets NF F 16-101/102 railway standards. Protective treatment conforms to IEC 60068 and DIN 50016. Standard Schneider declarations (RoHS, REACH, CE) apply to the TeSys K range."},{"question":"What is the physical size of this contactor?","answer":"Width 90 mm, height 58 mm, depth 57 mm. It's a panel-mount unit with IP20 finger-safe terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K1601F72","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K1601F72 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}