{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K16105E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K16105E7","canonicalUrl":"https://aoctrl.com/schneider/LC2K16105E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K16105E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 48 V AC coil, preassembled with reversing power busbar.","salesMarkdown":"The AC-3 rating of 16 A at 440 V governs motor switching — that is the current the contactor can make and break under full-load motor starting. The 48 V AC coil pull-in voltage must match the control transformer tap; a coil outside ±10 % of nominal may not hold closed under brownout. IP20 finger-safe terminals (VDE 0106) mean it is intended for enclosed panel mounting, not exposed washdown areas. The V1 flame-retardance rating per UL 94 and NF F 16-101 is a material-level safety property for rail and industrial enclosures. The 90 mm width × 58 mm height × 57 mm depth footprint clips onto standard DIN rail. The preassembled reversing busbar saves one wiring step — incoming line lands on the common terminals, and the two contactor coils are interlocked via the built-in mechanical linkage so both cannot close simultaneously. Operating altitude is 2000 m without derating; above that, the dielectric withstand drops and the contactor must be de-rated per IEC 60947.","metaTitle":"Schneider TeSys K LC2K16105E7 Reversing Contactor, 16 A, 48","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 16 A at 440 V, 48 V AC coil. Sourced to order against RFQ. IP20, V1 flame retardance.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dd0a6b927120a2b950f442f7cf4e956a.pdf","sourceUrl":"https://www.se.com/mk/en/product/LC2K16105E7/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-no-48-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K16105E7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this reversing contactor?","answer":"AC-3 motor-switching rating of 16 A at 440 V, 48 V AC coil, 3 NO main poles, IP20 finger-safe protection, and V1 flame retardance per UL 94."},{"question":"How do I source this obsolete part?","answer":"Through surplus or broker channels. We source it to order against an RFQ, verifying condition and traceability before shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K16105E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K16105E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}