{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K16105FC7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K16105FC7","canonicalUrl":"https://aoctrl.com/schneider/LC2K16105FC7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K16105FC7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 16 A, 1 NO, 127 V AC coil, preassembled with reversing power busbar.","salesMarkdown":"The Schneider TeSys K LC2K16105FC7 is a reversing contactor — three poles, normally open, with a 127 V AC coil. It's rated for AC-3 duty up to 16 A at 440 V, which means it's sized for reversing a three-phase motor of about 7.5 kW (10 hp) on a 400 V line. The AC-4 rating covers plugging and inching, so it'll handle the occasional reversal under load without welding the contacts. That's a time-saver on a panel build — just mount it, land the line and load, and you're done with the reversing circuit. This contactor lives inside an IP20 enclosure — no washdown, no outdoor exposure. It's meant for a dry control cabinet, DIN-rail mounted, with the gland plate keeping dust out. Storage range goes from -50 to 80 °C, which covers shipping and spares on a shelf. Altitude derating kicks in above 2000 m — if you're installing at elevation (say, a mine or high-altitude plant), you'll need to reduce the current or add forced cooling. ## Tough enough for the route Out here in the grease, vibration kills contacts. This one's tested to 4 Gn closed, 2 Gn open across 5–300 Hz, and shock-rated at 10–15 Gn depending on axis. That's enough for a conveyor drive or a pump skid — it won't chatter open on a bumpy line. Flame retardance meets UL 94 V1 and NF F 16-101/102, so it's acceptable for rail and transit applications where the fire code is strict.","metaTitle":"Schneider TeSys K LC2K16105FC7 Reversing Contactor, 3P, 16 A","metaDescription":"Schneider TeSys K reversing contactor, 3P, AC-3 <=440 V 16 A, 1 NO, 127 V AC coil. Active production. IP20. Preassembled reversing busbar. Order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LC2K16105FC7","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NO, 127 V AC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/85f888ac162f1a2cbc59e6b7ddd49873.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2K16105FC7/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-no-127-v-ac-coil/"},"ai":{"faq":[{"question":"What are its key ratings?","answer":"Three-pole reversing contactor, AC-3 rated 16 A at ≤440 V, 127 V AC coil. Rated operational voltage up to 690 V AC. Preassembled with reversing power busbar."},{"question":"What is the closest alternative in the TeSys K family?","answer":"The standard (non-reversing) TeSys K contactor with the same coil voltage and pole configuration is a direct functional match for forward-only duty. For reversing, this LC2K unit is the pre-assembled solution — no need to build the interlock externally."},{"question":"What compliance documentation is available?","answer":"The contactor carries UL 94 V1 flame retardance, NF F 16-101/102 for rail fire safety, and IP20 per VDE 0106. Shock and vibration testing follows IEC 60068-2-27 and IEC 60068-2-6."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K16105FC7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K16105FC7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}