{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K16105R7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K16105R7","canonicalUrl":"https://aoctrl.com/schneider/LC2K16105R7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K16105R7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 440 V AC coil, IP20, preassembled with reversing power busbar.","salesMarkdown":"Rated AC-3 ≤440 V 16 A, it handles reversing duty on a motor load up to that current; AC-3 is the motor-switching category per IEC 60947-4-1, so the 16 A figure is the real-world current for starting and stopping a squirrel-cage induction motor, not a resistive-heater rating. The coil is 440 V AC, matching a common control voltage in European 400 V three-phase panels. Operating temperature spans -25 to 50 °C, with storage from -50 to 80 °C; the 2000 m altitude rating without derating covers most industrial sites below that elevation. This reversing contactor is sized for a control panel — the 90 mm width, 58 mm height, and 57 mm depth fit a standard DIN-rail footprint alongside other TeSys K components. The preassembled reversing busbar saves panel-build time: no separate interlock wiring, just land the motor leads and control coil. Mechanical robustness is specified for shock and vibration — 10 Gn on Y and Z axes with contactor closed, 4 Gn vibration closed at 5–300 Hz — so it holds in on mobile equipment or near rotating machinery. Flame retardance meets V1 per UL 94 and Requirement 2 per NF F 16-101/102, which matters for rail and transit applications where fire-smoke-toxicity compliance is mandatory. The protective treatment conforms to IEC 60068 and DIN 50016, covering corrosion resistance in humid or mildly aggressive atmospheres.","metaTitle":"Schneider TeSys K LC2K16105R7 Reversing Contactor, 3P, 16 A","metaDescription":"Schneider TeSys K reversing contactor LC2K16105R7, 3P, AC-3 <=440 V 16 A, 1 NO, 440 V AC coil. Active production. IP20. Preassembled reversing busbar. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LC2K16105R7","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NO, 440 V AC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8d45201709a98f0ec2c1a8140b116879.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2K16105R7/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-no-440-v-ac-coil/"},"ai":{"faq":[{"question":"What are the key ratings for this reversing contactor?","answer":"AC-3 motor-switching rating is 16 A at ≤440 V. The coil is 440 V AC. It is a 3-pole (3 NO) reversing contactor with IP20 finger protection. Operating temperature range is -25 to 50 °C."},{"question":"What compliance documentation does this part carry?","answer":"Flame retardance is V1 per UL 94 and Requirement 2 per NF F 16-101/102. Protective treatment conforms to IEC 60068 and DIN 50016. IP20 per VDE 0106. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6."},{"question":"What is the physical size of the LC2K16105R7?","answer":"Width 90 mm, height 58 mm, depth 57 mm. DIN-rail mountable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K16105R7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K16105R7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}