{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K16105U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K16105U7","canonicalUrl":"https://aoctrl.com/schneider/LC2K16105U7","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K16105U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 230…240 V AC coil, IP20.","salesMarkdown":"Its headline rating is AC-3 duty at 16 A up to 440 V — the current it can switch under motor starting conditions (inrush and breaking) without welding contacts. The contactor measures 90 mm wide by 58 mm high by 57 mm deep. ## Mechanical and environmental robustness Rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: contactor closed withstands 10 Gn on X axis, 15 Gn on Y and Z axes (11 ms half-sine); open state withstands 6 Gn on X, 10 Gn on Y and Z. Vibration resistance is 4 Gn closed, 2 Gn open across 5–300 Hz. Flame retardance meets V1 per UL 94 and NF F 16-101/102. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance.","metaTitle":"TeSys K LC2K16105U7 Reversing Contactor, 3P, AC-3 16A, 230-2","metaDescription":"Obsolete TeSys K reversing contactor, 3P, AC-3 16 A at 440 V, 230-240 V AC coil. Sourced to order against RFQ. IP20, 57 mm depth.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","Height":"58 mm","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-4 AC-3","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/73c40e9d15ee79192f255f90b3b183a8.pdf","sourceUrl":"https://www.se.com/mk/en/product/LC2K16105U7/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-no-230-240-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC2K16105U7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC2K16105U7?","answer":"It is a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 230…240 V AC coil. The IP20 enclosure protects against finger contact in a panel."},{"question":"What is the physical size of the LC2K16105U7?","answer":"Width 90 mm, height 58 mm, depth 57 mm."},{"question":"What compliance documentation is available for the LC2K16105U7?","answer":"The part carries V1 flame retardance per UL 94 and conforms to NF F 16-101/102. Protective treatment meets IEC 60068 and DIN 50016. No RoHS or REACH statements are in the record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K16105U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K16105U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}