{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC2K16107FC72","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC2K16107FC72","canonicalUrl":"https://aoctrl.com/schneider/LC2K16107FC72","factsUrl":"https://aoctrl.com/api/mcp/products/LC2K16107FC72","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys K reversing contactor, LC2K16107FC72, 3P, AC-3 <=440 V 16 A, 1 NO auxiliary, 127 V AC coil, IP20, preassembled with reversing busbar.","salesMarkdown":"The LC2K16107FC72 is a TeSys K reversing contactor from Schneider Electric — a 3-pole unit rated AC-3 at 16 A up to 440 V, with a 127 V AC coil and one normally open auxiliary contact. The AC-3 rating is the motor-switching duty class per IEC 60947-4-1: 16 A means it can handle a 3-phase induction motor drawing that current during starting and stopping, which is the real-world load for reversing starters on conveyors, pumps, or fans. The part ships preassembled with the reversing power busbar, so you don't need to source a separate mechanical interlock kit for the forward/reverse pair. ## Fit and integration details The 127 V AC coil is a common control voltage in older North American installations and some industrial sites running 120 V control transformers — verify your control circuit matches before wiring. ## Mechanical and environmental robustness Rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: contactor stays closed under 10 Gn on Y and Z axes, 6 Gn on X when open. Vibration tolerance is 4 Gn closed, 2 Gn open across 5–300 Hz. That's enough for most industrial machinery, including conveyors and compressors mounted near the source. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is relevant for rail and transport applications where fire-smoke-toxicity requirements apply.","metaTitle":"Schneider TeSys K LC2K16107FC72 Reversing Contactor, 3P, 16","metaDescription":"Schneider TeSys K reversing contactor LC2K16107FC72, 3P, AC-3 <=440 V 16 A, 1 NO aux, 127 V AC coil, IP20. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"57 mm","Range":"TeSys","Width":"90 mm","title":"LC2K16107FC72","Height":"58 mm","description":"TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NO, 127 V AC coil","Product name":"TeSys K","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102","Device short name":"LC2K","Poles description":"3P","Device application":"Control","Operating altitude":"2000 m without derating","Device presentation":"Preassembled with reversing power busbar","Protective treatment":"TC conforming to IEC 60068 TC conforming to DIN 50016","Utilisation category":"AC-3 AC-4","Contactor application":"Motor control","Mechanical robustness":"Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to VDE 0106","Product or component type":"Reversing contactor","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-50...80 °C","Ambient air temperature for operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/16b350690e0198adde014a29fdb0a859.pdf","sourceUrl":"https://www.se.com/ie/en/product/LC2K16107FC72/tesys-k-reversing-contactor-3p-ac3-440-v-16-a-1-no-127-v-ac-coil/"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to LC2K16107FC72 in this component family?","answer":"Within the TeSys K series, the closest sibling is a reversing contactor with the same 3-pole AC-3 16 A rating but a different coil voltage. The LC2K16107FC72 uses a 127 V AC coil; if your control voltage differs, match the coil code suffix. No direct pin-compatible substitute outside the series is listed — the TeSys K footprint is specific to this family."},{"question":"What is LC2K16107FC72's listed depth (57 mm) on this component line?","answer":"The depth is 57 mm, which is the dimension from the mounting surface to the front of the contactor body — not including the coil terminals or auxiliary contact block if added."},{"question":"What is LC2K16107FC72's listed range (TeSys) on this component line?","answer":"The range is TeSys, specifically the TeSys K sub-family of compact contactors and reversing contactors for motor control up to 16 A AC-3."},{"question":"What compliance documentation does this brand provide for LC2K16107FC72 (RoHS, REACH, UL, IEC)?","answer":"The part carries IEC 60947-4-1 compliance for contactors, UL 94 V1 flame retardance, and IP20 per VDE 0106. RoHS and REACH declarations are standard for Schneider TeSys products but are not explicitly listed in this record — confirm with the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC2K16107FC72","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC2K16107FC72 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}