{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC3D32AM7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC3D32AM7","canonicalUrl":"https://aoctrl.com/schneider/LC3D32AM7","factsUrl":"https://aoctrl.com/api/mcp/products/LC3D32AM7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D series, LC3D32AM7 star delta starter, 32 A rated operational current, 220 V AC coil, 3 x 3P (3 NO) power poles, IP20 front face.","salesMarkdown":"The Schneider LC3D32AM7 is a TeSys D star delta starter, pre-wired for reduced-voltage starting of three-phase induction motors. It switches motor loads under AC-3 duty, rated at 32 A, with a 220 V AC coil. The contact arrangement is 3 x 3P (3 NO), meaning it opens and closes three power poles per phase for the star and delta contactors. The IP20 front face protection means it is safe from finger contact but not sealed against moisture — it belongs inside a control cabinet, not on a washdown line. It operates across -40 to 70 °C at rated coil voltage and can be stored from -60 to 80 °C, which covers most plant-floor conditions without derating up to 3000 m altitude. The AC-3 utilisation category rating of 32 A is the key selection parameter — it tells you the starter can switch a three-phase squirrel-cage motor up to that current during starting and plugging. Do not confuse this with an AC-1 resistive rating; for motor loads, AC-3 is the governing figure. The 220 V AC coil voltage is fixed — verify your control circuit matches. The pre-wired presentation means the internal star-delta interconnections are factory-assembled, reducing panel wiring time but also meaning the contactor set is not field-configurable for other topologies. Flame retardance V1 per UL 94 and fire resistance to 850 °C per IEC 60695-2-1 mean the housing materials meet the self-extinguishing and glow-wire standards required for panel-mounted equipment in most industrial and commercial installations.","metaTitle":"Schneider LC3D32AM7 TeSys D Star Delta Starter, 32 A, 220 V","metaDescription":"Obsolete Schneider TeSys D LC3D32AM7 star delta starter. 32 A, 220 V AC coil, 3 x 3P NO contacts. Sourced to order against RFQ. Confirm fit for your BOM line.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Range":"TeSys","Product name":"TeSys D","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Device short name":"LC3D","Poles description":"3 x 3P","Climatic withstand":"conforming to IACS E10 conforming to IEC 60947-1 Annex Q category D","Operating altitude":"3000 m without derating","Device presentation":"Pre-wired","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-3","Contactor application":"Motor control","Mechanical robustness":"Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 8 Gn for 11 ms","IP degree of protection":"IP20 front face conforming to IEC 60529","Product or component type":"Star delta starter","Power Pole Contact Composition":"3 x 3 NO","[Ue] rated operational voltage":"Power circuit: 10 MOhm for signalling circuit","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...70 °C at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/622d0d2a696c12d653ac1710f5aa02d1.pdf","sourceUrl":"https://www.se.com/uk/en/product/LC3D32AM7/tesys-d-star-delta-starter-3-x-3p-3-no-32-a-220-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC3D32AM7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the LC3D32AM7?","answer":"No official successor order code is listed by Schneider. A parametric substitute would need to match the 32 A AC-3 rating, 220 V AC coil, and 3 x 3P NO contact arrangement of the TeSys D star delta starter. Confirm fit with your motor data and control voltage before specifying a replacement."},{"question":"What is the LC3D32AM7's range and product name?","answer":"It belongs to the TeSys range and the product name is TeSys D."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC3D32AM7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC3D32AM7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}